4 how to configure, Opceip ethernet/ip, 1 ip settings – GE Industrial Solutions AF-600 FP OPCEIP EtherNet_IP User Manual

Page 16

Advertising
background image

4 How to Configure

4.1.1 IP Settings

All IP-related parameters are located in parameter group EN-##:

EN-00

IP Address Assignment

EN-01

IP Address

EN-02

Subnet Mask

EN-03

Default Gateway

EN-04

DHCP Server

EN-05

Lease Expires

EN-06

Name Servers

EN-07

Domain Name

EN-08

Host Name

EN-09

Physical Address

The OPCEIP option offers several ways of IP address assignment.

Setting up drive with manual assigned IP address:

Par.

Name

Value

EN-00

IP Address Assignment

[0] MANUAL

EN-01

IP Address

192.168.0.xxx*

EN-02

Subnet Mask

255.255.255.0*

EN-03

Default Gateway

optional

*= Class C IP address example. Any valid IP address can be entered.

NB!
A power-cycle is necessary after setting the IP parameters manually.

Setting up drive with automatic (BOOTP/DHCP) assigned IP address:

Par.

Name

Value

EN-00

IP Address Assignment

[1] DHCP/[2] BOOTP

EN-01

IP Address

Read only

EN-02

Subnet Mask

Read only

EN-03

Default Gateway

Read only

By IP address assigned by DHCP/BOOTP server, the assigned IP Address and Subnet Mask can be read out in par. EN-01 and EN-02. In par. EN-04 DHCP Server,
the IP address of the found DHCP or BOOTP server is displayed. For DHCP only: The remaining lease-time can be read-out in par. EN-05 Lease Expires.

Par. EN-09, Physical Address reads out the MAC address of option, which is also printed on the label of the option. If using fixed leases together with DHCP or
BOOTP, the physical MAC address is linked with a fixed IP address.

NB!
If no DHCP or BOOTP reply has been received after 4 attempts (e.g. if the DHCP/BOOTP server has been powered off), the option will fallback to the last good
known IP address.

OPCEIP EtherNet/IP

15

4