4.1.3 Configuring the Scanner

EDS file
GE provides a generic English EDS (Electronic Data Sheet) file covering all voltage and power sizes, for off-line configuration.

The EDS file can be downloaded from:
www.geelectrical.com/drives

NB!
The current version of the major EtherNet/IP configuration tools does not support EDS-files for EtherNet/IP devices.

Configuring a Rockwell Master
For configuring a AF-650 GP/AF-600 FP with OCPEIP for operation with a Rockwell (Allen-Bradley) Scanner via EtherNet/IP, the AF-650 GP must be added as a
Generic Ethernet Module.

Under the General-tab, enter information about: Name of device, IP Address,
Assembly Instance and Data size

NB!
Under Configuration in the Connection Parameters a “4” must be entered as Assembly Instance.

NB!
Please note that the example shows a 20/70 assembly instance connection. This requires to be set to: ODVA.
Other supported connections are shown in section: I/O Assembly Instanced.

Under the Connection-tab, enter information about: RII and fault conditions.

OPCEIP EtherNet/IP