Opceip ethernet/ip – GE Industrial Solutions AF-600 FP OPCEIP EtherNet_IP User Manual

Page 57

Advertising
background image

Class ID 0x06 Connection Manager

Attribute

Access

Name

Data Type

Description

1

Get

Open Requests

UINT

Number of Forward Open requests received

2

Get

Open Format Rejects

UINT

Number of Forward Open requests rejected due to bad format

3

Get

Open Resource Rejects

UINT

Number of Forward Open requests rejected due to lack of resources

4

Get

Open Other Rejects

UINT

Number of Forward Open requests rejected due to other reasons

5

Get

Close Requests

UINT

Number of Forward Close requests received

6

Get

Close Format Requests

UINT

Number of Forward Close requests rejected due to bad format

7

Get

Close Other Requests

UINT

Number of Forward Close requests rejected due to other reasons

8

Get

Connection Timeouts

UINT

Number of connection timeouts

9

Get

Connection Entry List Struct of: NumCon-
nEntries

INT

Number of connection entries ConnOpenBits ARRAY of BOOL List of
connection data

Table 8.3: Instance Attributes

Class ID 0x28 Motor Data Object

Attribute

Access

Name

Data Type

Parameter

Description

1

Get

Number of Attributes supported

USINT

-

7

2

Get

List of attributes supported

Array of USINT

-

3,6,7,8,9,12,15

3

Get/Set

Motor Type

USINT

P-20

3: PM sync. motor (AF-650 GP only)
7: Squirrel cage induction motor

6

Get/Set

Rated Current

UINT

P-03

Unit: 100 mA

7

Get/Set

Rated Voltage

UINT

F-05

Unit: Volt

8

Get/Set

Rated Power

UDINT

P-07

Unit: Watt

9

Get/Set

Rated Frequency

UINT

F-04

Unit: Hertz

12

Get/Set

Pole Count

UINT

P-01

Number of poles in motor

15

Get/Set

Base Speed

UINT

P-06

Unit: RPM

Table 8.4: Instance Attributes

NB!
Class ID 0x28 is only available if ODVA profile is selected in par.O-10 Control Word Profile.

Class ID 0x29 Control Supervisor Object

Attribute

Access

Name

Data Type

Description

1

Get

Number of Attributes supported

USINT

12

2

Get

List of supported Attributes

Array of USINT

3,4,4,5,6,7,8,9,10,11,12,13,15

3

Get/Set

Run 1 (forward)

Boolean

Drive CTW Bit 6 = Run1 XOR Run2
Drive CTW Bit15 = 0

4

Get/Set

Run 2 (reverse)

Boolean

Drive CTW Bit 6 = Run1 XOR Run2
Drive CTW Bit15 = 1

5

Get/Set

Network Control

Boolean

Parameter EN-32 value written from option

6

Get

State

USINT

The state of the CIP state-machine

7

Get

Running 1

Boolean

Run1 AND bit 11 in Drive STW

8

Get

Running 2

Boolean

Run2 AND bit 11 in Drive STW

9

Get

Ready

Boolean

STATE_ENABLED or STATE_STOPPING or
STATE_FAULT_STOP from state-machine

10

Get

Faulted

Boolean

Bit 3 in Drive STW

11

Get

Warning

Boolean

Bit 7 in Drive STW

12

Get/Set

Fault reset

Boolean

Bit 7 in Drive CTW

13

Get

Fault Code

UINT

Mapping of par. DR-90 Alarm Word to CIP specific fault
codes

15

Get

Control from net

Boolean

Parameter EN-31 value written from option

Table 8.5: Instance Attributes

OPCEIP EtherNet/IP

56

8

Advertising