background image

CIP Malfunction Code

Meaning

Drive-Code Alarmword

CIP Malfunction Meaning

CIP Classification

0

No alarm

0000 0000

No fault

-

0

unused

0000 0001

No fault

-

4210

Drive over temperature

0000 0002

Excessive Device Temperature

mar

2240

Earth fault

0000 0004

Short to earth

mau

0

unused

0000 0008

No fault

-

8100

Controlword timeout

0000 0010

Communication

mir

2310

Overcurrent

0000 0020

Continuous Overcurrent

mau

8302

Torque limit

0000 0040

Torque limiting

mar

4310

Motor thermistor

0000 0080

Excess Drive Temperature

mar

4310

Motor Electronic Thermal Over-
load over temp

0000 0100

Excess Drive Temperature

mar

2311

Inverter overloaded

0000 0200

Current inside the device, No. 1

mar

3220

DC Link undervoltage

0000 0400

Undervoltage inside the Device

mar

3210

DC Link overvoltage

0000 0800

Overvoltage inside the device

mar

2130

Short circuiting

0000 1000

Short Circuit

mau

2213

Inrush fault

0000 2000

Overcurr. marduring startup

3130

Mains phase loss

0000 4000

Phase Failure

mau

5210

Auto tune fail

0000 8000

Measurement Circuit

mir

1000

Live zero fault

0001 0000

General fault

mar

6100

Internal fault

0002 0000

Internal software fault

mau

7110

Brake resistor power limit

0004 0000

Brake Chopper

mau

3300

Motor phase U missing

0008 0000

Output voltage

mau

3300

Motor phase V missing

0010 0000

Output voltage

mau

3300

Motor phase W missing

0020 0000

Output voltage

mau

8100

Network Comm. fault

0040 0000

Communication

mir

5112

24V supply fault

0080 0000

+24V Power supply

mau

3100

Mains failure

0100 0000

Mains Voltage

mar

5110

1,8V supply fault

0200 0000

Low voltage power supp.

mau

7110

Brake resist. short circ.

0400 0000

Brake chopper

mar

7110

Brake chopper fault

0800 0000

Brake chopper

mar

0

unused

1000 0000

No fault

-

0

unused

2000 0000

No fault

-

0

unused

4000 0000

No fault

-

0

unused

8000 0000

No fault

-

Table 8.6: Attribute 13 “Fault Code”

Mir = Minor Recoverable
Mar = Major Recoverable
Mau = Major Unrecoverable

Service Code

Service Name

Service Description

0Eh

Get_Attribute_Single

Returns contents of specified attribute

10h

Set_Attribute_Single

Sets the contents of specified attribute

05h

Reset

Resets drive to it’s start-up state.

Table 8.7: Services supported

NB!
Class ID 0x29 is only available if ODVA profile is selected in par.O-10 Control Word Profile.

OPCEIP EtherNet/IP