background image

Class ID 0xF6 Link Object
Three instances of the Link Object are implemented:

-

Instance 1 and 2 relates to the physical Port 1 and 2 of the option.

-

Instance 3 relates to the internal interface of the option, after the build-in switch.

Attrib-

ute

Access

Rule

Name

Data Type

Description of Attribute

Parameter

in drive

1

Get

Interface Speed

UDINT

Interface speed in Mbps (e.g., 0, 10, 100, 1000, etc.)

EN-13

2

Get

Interface Flags

DWORD

Interface status flags

-

3

Get

Physical Address

ARRAY of 6 USINTs

MAC layer address

EN-09

4

Get

Interface Counters

STRUCT of

In Octets

UDINT

Octets received on the interface

EN-98 [0]

In Ucast Packets

UDINT

Unicast packets received on the interface

EN-98[1]

In NUcast Packets

UDINT

Non-unicast packets received on the interface

EN-98[2]

In Discards

UDINT

Inbound packets received on the interface but discarded

EN-98[3]

In Errors

UDINT

Inbound packets that contain errors (does not include In Discards)

EN-98 [4]

In Unknown Protos

UDINT

Inbound packets with unknown protocol

EN-98[5]

Out Octets

UDINT

Octets sent on the interface

EN-98[6]

Out Ucast Packets

UDINT

Unicast packets sent on the interface

EN-98[7]

Out NUcast Packets

UDINT

Non-unicast packets sent on the interface

EN-98[8]

Out Discards

UDINT

Outbound packets discarded

EN-98[9]

Out Errors

UDINT

Outbound packets that contain errors

EN-98[10]

5

Get

Media Counters

STRUCT of:

Media-specific counters

Alignment Errors

UDINT

Frames received that are not an integral number of octets in length

EN-99[0]

FCS Errors

UDINT

Frames received that do not pass the FCS check

EN-99[1]

Single Collisions

UDINT

Successfully transmitted frames which experienced exactly one colli-
sion

EN-99[2]

Multiple Collisions

UDINT

Successfully transmitted frames which experienced more than one
collision

EN-99[3]

SQE Test Errors

UDINT

Number of times SQE test error message is generated

EN-99[4]

Deferred Transmis-
sions

UDINT

Frames for which first transmission attempt is delayed because the
medium is busy

EN-99[5]

Late Collisions

UDINT

Number of times a collision is detected later than 512 bit times into the
transmission of a packet

EN-99[6]

Excessive Collisions

UDINT

Frames for which transmission fails due to excessive collisions

EN-99[7]

MAC Transmit Errors

UDINT

Frames for which transmission fails due to an internal MAC sub layer
transmit error

EN-99[8]

Carrier Sense Errors

UDINT

Times that the carrier sense condition was lost or never asserted when
attempting to transmit a frame

EN-99[9]

Frame Too Long

UDINT

Frames received that exceed the maximum permitted frame size

EN-99[10]

MAC Receive Errors

UDINT

Frames for which reception on an interface fails due to an internal MAC
sub layer receive error

EN-99[11]

6

Set

Interface Control

STRUCT of:

Configuration for physical interface

-

Control Bits

WORD

Interface Control Bits

-

Forced Interface Speed UINT

Speed at which the interface shall be forced to operate Speed in Mbps
(10, 100, 1000, etc.)

-

7

Get

Interface Label

SHORT_STRING

Human readable identification

-

8

Get

Link List Size

USINT

Number of members in Link List

-

9

Get

Link List

ARRAY OF UINT

Link List between internal and all according external interfaces

-

Table 8.11: Instance Attributes