Opceip ethernet/ip – GE Industrial Solutions AF-600 FP OPCEIP EtherNet_IP User Manual

Page 35

Advertising
background image

[7]

Select setup 1

Changes the set-up upon reestablishment of communication following a control word time-out. If com-
munication resumes causing the time-out situation to disappear, par.O-05 End-of-Timeout Function
defines whether to resume the set-up used before the time-out or to retain the set-up endorsed by the
time-out function.

[8]

Select setup 2

See [7] Select setup 1

[9]

Select setup 3

See [7] Select setup 1

[10]

Select setup 4

See [7] Select setup 1

NB!
The following configuration is required in order to change the set-up after a time-out:
Set par. K-10 Active Set-up to [9] Multi set-up and select the relevant link in par. K-12 This Set-up Linked to.

O-05 End-of-Timeout Function

Option:

Function:

Select the action after receiving a valid control word following a time-out. This parameter is active only
when par. O-04 Control Word Timeout Function is set to [Set-up 1-4].

[0]

Hold set-up

Retains the set-up selected in par. O-04 Control Word Timeout Function and displays a warning, until
par. O-06 Reset Control Word Timeout toggles. Then the drive resumes its original set-up.

[1] *

Resume set-up

Resumes the set-up active prior to the time-out.

O-06 Reset Control Word Timeout

This parameter is active only when Hold set-up [0] has been selected in par.O-05 End-of-Timeout Function.

Option:

Function:

[0] *

Do not reset

Retains the set-up specified in par.O-04 Control Word Timeout Function, following a control word time-
out.

[1]

Do reset

Returns the frequency converter to the original set-up following a control word time-out. The frequency
converter performs the reset and then immediately reverts to the Do not reset [0] setting

O-10 Control Word Profile

Select the interpretation of the control and status words corresponding to the installed network. Only the selections valid for the network installed in slot A will
be visible in the Keypad display.
For guidelines in selection of GE Drive profile [0] and PROFIdrive profile [1] please refer to the Serial communication via RS 485 Interface section.
For additional guidelines in the selection of PROFIdrive profile [1], ODVA [5] and CANopen DSP 402 [7], please refer to the Operating Instructions for the installed
network.

Option:

Function:

[0] *

Drive Profile

[1]

PROFIdrive profile

[5]

ODVA

[7]

CANopen DSP 402

O-13 Configurable Status Word STW

Option:

Function:

This parameter enables configuration of bits 12 – 15 in the status word.

[0]

No function

[1] *

Profile Default

Function corresponds to the profile default selected in par. O-10 Control Word Profile.

[2]

Alarm 68 Only

Only set in case of an Alarm 68.

[3]

Trip excl Alarm 68

Set in case of a trip, except if the trip is executed by an Alarm 68.

[16]

T37 DI status

The bit indicates the status of terminal 37.
“1” indicates T37 is high (normal)

OPCEIP EtherNet/IP

34

6

Advertising