5.3 ODVA Control Profile

5.3.1 Control Word under Instances 20/70 and 21/71

Set par.O-10 Control Word Profile to ODVA.

The control word in Instances 20 and 21 is defined as follows:

NB!
Bits 00 and 02 in Instance 20 are identical with bits 00 and 02 in the more extensive Instance 21.

Bit

Instance 20

Instance 21

Bit = 0

Bit =1

Bit = 0

Bit =1

00

Stop

Run

Fwd Stop

Run Fwd

01

-

-

Stop

Run Rev

02

No function

Fault reset

No function

Fault reset

03

-

-

-

-

04

-

-

-

-

05

-

-

-

Net Ctrl

06

-

-

-

Net Ref

07-15

-

-

-

-

Explanation of the Bits:
Bit 0, Run Fwd:
Bit 0 = "0" means that the drive has a stop command. Bit 0 = "1" leads to a start command and the drive will start to run the motor clockwise.

Bit 1, Run Rev:
Bit 1 = "0" leads to a stop of the motor. Bit 1 = "1" leads to a start of the motor.

Bit 2, Fault Reset:
Bit 2 = "0" means that there is no trip reset. Bit 2 = "1" means that a trip is reset.

Bit 3, No function:
Bit 3 has no function.

Bit 4, No function:
Bit 4 has no function.

Bit 5, Net Control:
Bit 5 = "0" means that the drive is controlled from the standard inputs. Bit 5 = "1" means that EIP controls the drive.

NB!
Please note that changes will affect parameters O-50 to O-56.