Opceip ethernet/ip – GE Industrial Solutions AF-600 FP OPCEIP EtherNet_IP User Manual

Page 59

Advertising
background image

Class ID 0x2A AC/DC Drive Object

Attribute

Access Rule

Information about

Data Type

Contents

1

Get

Number of Attributes Supported

USINT

12

2

Get

List of Attributes Supported

USINT

3,4,6,7,8,18,19,20,21,22,28,29

3

Get

At Reference

Boolean

Bit 8 of Drive STW

4

Get/Set

Network Reference

Boolean

value written to parameter "Net Reference"

6

Get/Set

Drive Mode

USINT

Mapping of values from parameter H-40

7

Get

Actual Speed

INT

See Attribute 22

8

Get/Set

Reference Speed

INT

See Attribute 22

18

Get/Set

Acceleration Time

UINT

Scaled with Attribute 28 and written to par. F-07

19

Get/Set

Deceleration time

UINT

Scaled with Attribute 28 and written to par. F-08

20

Get/Set

Low Speed Limit

UINT

Scaled with Attribute 22 and written to par. F-18

21

Get/Set

High Speed Limit

UINT

Scaled with Attribute 22 and written to par. F-17

22

Get/Set

Speed Scale

SINT

Forms the "Speed Reference" and "Main Actual Value" for the
Drive together with Attribute 7 and 8

28

Get/Set

Time Scale

SINT

Scaling factor for all time attributes

29

Get

Ref From Net

Boolean

value of parameter "Net Reference"

Table 8.8: Instance Attributes

Value of Attribute 6

ODVA Text

Value of par. H-40

Drive Text

0

Vendor specific

Remaining values not listed below

?

1

Open loop speed ctr.

0

Speed open loop

2

Closed loop speed ctr.

1

Speed closed loop

3

Torque Control

NA

NA

4

Process Control

NA

NA

5

Position Control

NA

NA

Table 8.9: Attribute 6 “Drive Mode”

NB!
Class ID 0x2A is only available if ODVA profile is selected in par.O-10 Control Word Profile.

Class ID 0xF5 Interface Object

Attribute

Access Rule

Name

Data Type

Description of Attribute

Parameter In
Drive

1

Get

Status

DWORD

Interface status

-

2

Get

Configuration Capability

DWORD

Interface capability flags

-

3

Get/Set

Configuration Control

DWORD

Interface control flags

-

4

Get

Physical Link Object

STRUCT of:

Path to physical link object

-

Path size

UINT

Size of Path

-

Path

Padded EPATH

Logical segments identifying the physical link ob-
ject

-

5

Get/Set

Interface Configuration

STRUCT of:

TCP/IP network interface configuration.

-

IP Address

UDINT

The device’s IP address.

EN-01

Network Mask

UDINT

The device’s network mask.

EN-02

Gateway Address

UDINT

Default gateway address

EN-03

Name Server

UDINT

Primary name server

EN-06 [0]

Name Server 2

UDINT

Secondary name server

EN-06[1]

Domain Name

STRING

Default domain name

EN-07

6

Get/Set

Host Name

STRING

Host name

EN-08

Table 8.10: Instance Attributes

OPCEIP EtherNet/IP

58

8

Advertising