Opceip ethernet/ip – GE Industrial Solutions AF-600 FP OPCEIP EtherNet_IP User Manual

Page 62

Advertising
background image

Service Code

Supported

Service Name

Description of Service

Class

Instance

0Eh

Yes

Yes

Get_Attribute_Single

returns contents of specified attribute

01h

Yes

Yes

Get_Attributes_All

returns predefined listing of object attributes

10h

No

Yes

Set_Attribute_Single

modifies attribute

4Bh

No

Yes

Get_Enum_String

reads enumerated strings from parameter instance

Table 8.15: Services supported

Class ID 0x10 Parameter Group Object

Attribute

Access

Rule

Name

Data Type

Description

Contents

1

Get

Group Name String

SHORT_STRING

represents group name

Name of Group from Drive

2

Get

Number of group members

UINT

amount of parameters in group

value of n

3

Get

1st group parameter (000-099)

UINT

instance number of Parameter Object

variable

4

Get

2nd group parameter (100-199)

UINT

instance number of Parameter Object

variable

Get

UINT

variable

n+2

Get

nth group parameter

UINT

instance number of Parameter Object

variable

Table 8.16: Instance Attributes

Class ID 0x64 – 0xC7 GE Objects
The CIP Class ID 100 to 199 (0x64 to 0xC7) gives access to all drive parameters.

Class (decimal)

GE Parameter range

100

F-##

101

E-##

102

C-##

103

P-##

104

H-##

105

K-##

106

AN-##

107

B-##

108

O-##

109

PB-##

110

SP-##

111

XC-##

112

DR-##

The class Instance and Attribute acts in the following way:

-

100 added to the parameter group = the value for the class.

-

100 added to the remaining parameter number = the value for the instance.

-

100 added to the array index of the parameter = the value for the attribute

Examples: (fictitious parameters)

-

Parameter K-01 [index 0] = Class 100; Instance 105; Attribute 100

-

Parameter H-40 [index 0] = Class 104; Instance 140; Attribute 100

-

Parameter AN-54 [index 9] = Class 106; Instance 154; Attribute 109

-

Parameter DN-01 [index 0] = Class 122; Instance 101; Attribute 100

All values in decimal.

All parameters are accessed in the Active setup (par. K-10 Active Set-up)

OPCEIP EtherNet/IP

61