4 how to configure the system, 1 configuring bacnet, Af-600fp bacnet – GE Industrial Solutions AF-600 FP BACnet User Manual

Page 16: 1 initialization procedure

Advertising
background image

4 How to Configure the System

4.1 Configuring BACnet

4.1.1 Initialization Procedure

The Initialization Procedure is explained by the flow chart given below:

Initialization Parameter

General Settings

Name

Parameter Number

Default Value

Setting for BACnet

Control Site

O-01

Digital and control word

Digital and control word

Control word source

O-02

Drive RS-485

Drive RS-485

ControlWord Timeout time

O-03

1.0 sec

1.0 sec

ControlWord Timeout Function

O-04

Off

Off

End of Timeout Function

O-05

Resume setup

Resume setup

Reset ControlWord Timeout

O-06

Do not reset

Do not reset

Diagnosis

O-07

Set up

Don’t care

ControlWord Profile

O-10

Drive protocol

Drive protocol

Drive Port Settings

Name

Parameter Number

Default Value

Setting for BACnet

Protocol

O-30

Drive

Drive Option

Address

O-31

1

1

Baud Rate

O-32

9600 baud

9600 baud

Minimum Response Delay

O-35

10 ms

10 ms

Max Response Delay

O-36

5000 ms

5000 ms

Table 4.1: 1) Please see also section: Parameter Overview >Parameter List.

AF-600FP BACnet

15

4