Af-600fp bacnet – GE Industrial Solutions AF-600 FP BACnet User Manual

Page 36

Advertising
background image

In LonWorks, the time-out function is also activated when the following SNVT's fail to be updated within the time period specified in par. O-03 Control Word Timeout
Time
:

nviStartStop

nviReset Fault

nviControlWord

nviDrvSpeedStpt

nviRefPcnt

nviRefHz

O-05 End-of-Timeout Function

Option:

Function:

Select the action after receiving a valid control word following a time-out. This parameter is active only
when par. O-04 Control Word Timeout Function is set to [Set-up 1-4].

[0]

Hold set-up

Retains the set-up selected in par. O-04 Control Word Timeout Function and displays a warning, until par.
O-06 Reset Control Word Timeout
toggles. Then the drive resumes its original set-up.

[1] *

Resume set-up

Resumes the set-up active prior to the time-out.

O-06 Reset Control Word Timeout

Option:

Function:

This parameter is active only when the choice Hold set-up [0] has been selected in par. O-05 End-of-
Timeout Function
.

[0] *

Do not reset

Retains the set-up specified in par. O-04 Control Word Timeout Function, [Select setup 1-4] following a
control time-out.

[1]

Do reset

Returns the drive to the original set-up following a control word time-out. When the value is set to Do
reset
[1], the drive performs the reset and then immediately reverts to the Do not reset [0] setting.

O-07 Diagnosis Trigger

Option:

Function:

This parameter has no function for LonWorks.

[0] *

Disable

[1]

Trigger on alarms

[2]

Trigger alarm/warn.

O-10 Control Word Profile

Option:

Function:

Select the interpretation of the control and status words corresponding to the installed network. Only the
selections valid for the network installed in slot A will be visible in the Keypad display.

[0] *

Drive Profile

[1]

PROFIdrive profile

[5]

ODVA

[7]

CANopen DSP 402

O-30 Protocol

Option:

Function:

Protocol selection for the integrated Drive (standard) Port (RS485) on the control card.
Parameter group BN-7# is only visible when Drive Option [9] is chosen.

[0] *

Drive

Communication according to the Drive Protocol as described in the AF-600 FP Design Guide, RS-485
Installation and Set-up
.

[1]

Drive MC

Same as Drive [0] but to be used when downloading SW to the drive or uploading dll file (covering infor-
mation regarding parameters available in the drive and their inter-dependencies) to Drive Control Tool
DCT10.

[2]

Modbus RTU

Communication according to the Modbus RTU protocol as described in the AF-600 FP Design Guide,
RS-485 Installation and Set-up.

AF-600FP BACnet

35

6