Object Id

Object Name

Read/Write

Changeable De-

scription

Non volatile ram

Store

Drive Par.

Alarm
notifi-

cation

Triggers Bus Time-

out

BO:30

Reserved output

E-90/30*

W/R

No

No

E-90/30

No

Yes

BO:31

Reserved output

E-90/31*

W/R

No

No

E-90/31

No

Yes

BO:36

Reserved output

E-90/26*

W/R

No

No

E-90/26

No

Yes

BO:37

Reserved output

E-90/27*

W/R

No

No

E-90/27

No

Yes

BO:38

Reserved output

E-90/28*

W/R

No

No

E-90/28

No

Yes

BO:39

Reserved output

E-90/29*

W/R

No

No

E-90/29

No

Yes

Table 5.1: Binay outputs cont.
*) Reserved for future options!

Object ID

Object Name

Read / Write

Changeable De-
scription

Non volatile ram
Store

Drive Par.

Alarm
notifi-
cation

Triggers Bus
Timeout

BV:0

Com. Fault

R

No

NA

BACnet option

Yes

No

BV:1

Start

W/R

No

No

CTW

No

Yes

BV:2

Coasting

W/R

No

No

CTW, Bit 3 =0

No

Yes

BV:3

CW/CCW

W/R

No

No

CTW bit 15=1

No

Yes

BV:4

Jog

W/R

No

No

CTW bit 0 =1

No

Yes

BV:5

Reset

W

No

No

CTW bit 07 = 1

No

Yes

BV:6

Reset Kwh Counter

W

No

No

ID-06

No

NO

BV:7

Reset Running Hours
Counter

W

No

No

ID-07

No

NO

BV:10

Drive Ready

R

No

NA

STW Bit 01

No

No

BV:11

Reverse

R

No

NA

STW Bit 15

No

No

BV:12

Speed = reference

R

No

NA

STW Bit 08

No

No

BV:13

Bus control

R

No

NA

STW Bit 09

No

No

BV:14

Tripped

R

No

NA

STW Bit 03

Yes

No

BV:15

Triplock

R

No

NA

STW Bit 06

Yes

No

BV:16 -20

Reserved

R

No

Table 5.1: Binary values

AF-600FP BACnet

24