Af-600fp bacnet – GE Industrial Solutions AF-600 FP BACnet User Manual

Page 27

Advertising
background image

Object ID

Object Name

Read / Write

Changeable De-

scription

Non volatile ram

Store

Drive Par.

Alarm
notifi-

cation

Triggers Bus

Timeout

BV:80

Broken Belt

R

No

NA

DR-91/08

Yes

BV:81

Discharge High

R

No

NA

DR-91/08

Yes

BV:82

Start fault

R

No

NA

DR-91/10

Yes

BV:83

Speed limit

R

No

NA

DR-91/11

Yes

BV:84

State fault DR-91/12

R

No

NA

DR-91/12

Yes

BV:85

State fault DR-91/13

R

No

NA

DR-91/13

Yes

BV:86

State fault DR-91/14

R

No

NA

DR-91/14

Yes

BV:87

State fault DR-91/15

R

No

NA

DR-91/15

Yes

BV:88

KTY Temperature error

R

No

NA

DR-91/16

Yes

BV:89

Drive Fan error

R

No

NA

DR-91/17

Yes

BV:90

ECB error

R

No

NA

DR-91/18

Yes

BV:91

Alarm 1692/19

R

No

NA

DR-91/19

Yes

BV:92

Alarm 1692/20

R

No

NA

DR-91/20

Yes

BV:93

Alarm 1692/21

R

No

NA

DR-91/21

Yes

BV:94

Alarm 1692/22

R

No

NA

DR-91/22

Yes

BV:95

Alarm 1692/23

R

No

NA

DR-91/23

Yes

BV:96

Alarm 1692/24

R

No

NA

DR-91/24

Yes

BV:97

Alarm 1692/25

R

No

NA

DR-91/25

Yes

BV:98

Alarm 1692/26

R

No

NA

DR-91/26

Yes

BV:99

Alarm 1692/27

R

No

NA

DR-91/27

Yes

BV:100

Alarm 1692/28

R

No

NA

DR-91/28

Yes

BV:101

Alarm 1692/29

R

No

NA

DR-91/29

Yes

BV:102

Alarm 1692/30

R

No

NA

DR-91/30

Yes

BV:103

Alarm 1692/31

R

No

NA

DR-91/31

Yes

BV:104

Brake Check

R

No

NA

DR-92/00

Yes

BV:105

Pwr. Card Temp

R

No

NA

DR-92/01

Yes

BV:106

Earth Fault

R

No

NA

DR-92/02

Yes

BV:107

Ctrl. Card Temp

R

No

NA

DR-92/03

Yes

BV:108

Crtl. Word TO

R

No

NA

DR-92/04

Yes

BV:109

Over Current

R

No

NA

DR-92/05

Yes

BV:110

Torque Limit

R

No

NA

DR-92/06

Yes

BV:111

Motor Th Over

R

No

NA

DR-92/07

Yes

BV:112

Motor Electronic Thermal

Overload Over

R

No

NA

DR-92/08

Yes

BV:113

Inverter overld.

R

No

NA

DR-92/09

Yes

BV:114

DC under Volt

R

No

NA

DR-92/10

Yes

BV:115

DC over Volt

R

No

NA

DR-92/11

Yes

BV:116

DC Voltage Low

R

No

NA

DR-92/12

Yes

BV:117

DC Voltage high

R

No

NA

DR-92/13

Yes

BV:118

Mains Ph. Loss

R

No

NA

DR-92/14

Yes

BV:119

No Motor

R

No

NA

DR-92/15

Yes

BV:120

Live Zero Error

R

No

NA

DR-92/16

Yes

Table 5.1: Binary values cont.

AF-600FP BACnet

26

5

Advertising