Af-600fp bacnet – GE Industrial Solutions AF-600 FP BACnet User Manual

Page 18

Advertising
background image

MS/TP running at 38.400 Baud

MAC address 20 for the AF-600 FP

BACnet Device Instance 0 1025

Highest number of a Master stack is 35

Start/stop of Drive from BACnet only

Reference from BACnet

Read status of Drive (Actual speed)

Set the following parameters:
Name

Parameter number

Value

Protocol

O-30

Drive option [9]

Address

O-31

20

Drive Port Baud Rate

O-32

38,400 Baud [4]

Coasting Select

O-50

Bus [1]

BACnet device Instance

BN-70

1025

MS/TP Max Masters

BN-72

35

After the parameters have been set according the table above, the drive has to be unpowered and repowered before the changes take effect. When the drive is
detected by the BMS, the drive can be controlled by BV:1, which will start the motor if set to [1]. Setting AV:0 will set the speed reference of the drive. The actual
speed can be monitored via AV:1. See also Analog Input- and Output Objects section.