7.2 LED Status

Check the LEDs. The two bi-colour LEDs on the BACnet card indicate the status of BACnet communication.

LED 1: Net Status

Phases

Status

Bi-colour LED

Power On.

Hardware Not OK

Red

Self test

Green

▂█▂█▂█▂█▂█

Running

Module OK

Green

██████████

Recoverable fault

Red

Data exchange Device communicating.

Green

LED 2 : Module Status

Phases

Status

Bi-colour LED

Power On.

Unrecoverable fault Drive is not responding on in-
ternal bus

Red

Self test configuration takes place

Green

▂█▂█▂█▂█▂█

Running

Module OK

Green

██████████

Recoverable

fault

• Configuration not OK e.g, P830
• Drive tripped

Red