2 bibbs, 3 example of a simple setup of bacnet, Af-600fp bacnet – GE Industrial Solutions AF-600 FP BACnet User Manual

Page 17: 2 control word time-out function, 1 bibb's

Advertising
background image

Digital/Bus settings

Name

Parameter Number

Default Value

Setting for BACnet

Coasting Select

O-50

Logic-or

Logic-or

Quick Stop Select

O-51

Logic-or

Logic-or

DC Brake Select

O-52

Logic-or

Logic-or

Start Select

O-53

Logic-or

Logic-or

Reversing Select

O-54

Logic-or

Logic-or

Set-up Select

O-55

Logic-or

Logic-or

Preset reference Select

O-56

Logic-or

Logic-or

BACnet settings

Name

Parameter Number

Default Value

Setting for BACnet

BACnet device Instance

BN-70

1

1

MS/TP Max Masters

BN-73

127

Depent on the Number of Masters in the

system

“I am” Service

BN-74

At power up

At power up

Initialisation Password

BN-75

“admin”

“admin”

4.1.2 Control Word Time-out Function

par. O-03 Control Word Timeout Time and par. O-04 Control Word Timeout Function are not enabled in this version of the BACnet option.

4.2 BIBBs

4.2.1 Bibb's

ReadProperty Service

ReadPropertyMultiple Service

WriteProperty Service

WritePropertyMultiple Service

ConfirmedEventNotification Service

UnconfirmedEventNotification Service

GetEventInformation Service

AcknowledgeAlarm Service

ReinitializeDevice Service

DeviceCommunicationControl Service

I-Have Service

Who-Has Service

Who-Is Service

I-am Service

TimeSynchronization

4.3 Example of a simple setup of BACnet

This example shows the necessary steps to set up the AF-600 FP BACnet interface with the following system requirements:

AF-600FP BACnet

16