5.2.3 Multi-state Input- and Output Objects

Multi-state Variable

Object Id

Object Name

Read/Write

Changeable De-
scription

Non volatile ram
Store

Drive Par.

Alarm notifi-
cation

Triggers Bus
Timeout

MSV:0

LC Controller State

R

No

Non

DR-38

No

No

MSV:1

Setup selection

W/R

No

Non

Bit13&14 in CTW

No

No

Mailbox variable

Object Id

Object Name

Read/Write

Changeable De-
scription

Non volatile ram
Store

Drive Par.

Alarm notifi-
cation

Triggers Bus Time-
out

MBV:0

Mailbox Write

W/R

No

Non

PCV part of the

send Drive tele-

gram

No

No

MBV:1

Mailbox Read

R

No

Non

PCV part of the

receive Drive

telegram

No

No

5.2.4 Real Time Clock Variable

The drive has a built-in real-time clock. The standard real-time clock has no battery back-up function, which will lead to a time stop if the Drive is unpowered.
Some BACnet Master's can be programmed to send out the date and time as a Broadcast Telegram on a regular basis. The BACnet will update the real-time clock
of the Drive if it receives this type of telegram: “Telegram”.

5.3 Drive Feedback to Network

The BACnet option provides several output variables (nvo’s) to the network, containing important drive -, motor- and I/O feedback data. The BACnet option transmits
bound network variables only and sends feedback data when there is a change in value.

Influence of the digital input terminals upon the Drive Control Mode, par. O-50 Coasting Select to par. O-56 Preset Reference Select
The influence of the digital input terminals upon control of the drive can be programmed in par. O-50 Coasting Select to par. O-56 Preset Reference Select.

NB!
par. O-01 Control Site overrules the settings in parameters O-50 to O-56.

Each of the digital input signals can be programmed to logic AND, logic OR, or to have no relation to the corresponding bit in the control word. In this way a specific
control command i.e. stop / coast, can be initiated by the network only, network AND Digital Input, or Ether Network OR Digital input terminal.

In order to control the drive via BACnet, par. O-50 Coasting Select must be set to either Bus [1], or to Logic AND [2] and par. O-01 Control Site
must be set to Digital and ctrl. word [0] or Controlword only [2].

More detailed information and examples of logical relationship options are provided in the Troubleshooting chapter.

AF-600FP BACnet

29

5