6 Parameters

6.1 Parameter Overview

6.1.1 Parameter List

Nr.

Title

Default value

Range

Conversion in-

dex

Data

type

O-01

Control Site

Dig. and ctrl. word [0]

[0 - 2]

-

5

O-02

Control Source

Drive RS485 [0]

[0 - 4]

-

5

O-03

Control Timeout Time

1 s

0.1 - 18000

- 1

7

O-04

Control Timeout Function

Off [0]

[0 - 10]

-

5

O-05

End-of-timeout Function

Hold set-up [0]

[0 - 1]

-

5

O-06

Reset Control Timeout

Do not reset [0]

[0 - 1]

-

5

O-07

Diagnosis Trigger

Disable [0]

[0 - 3]

-

5

O-10

Control Profile

Drive profile protocol [0]

[0 - x]

-

5

O-30

Protocol

Drive

O-31

Address

1

[0 – 255]

O-32

Baudrate

9600

[0 – 7]

O-33

Parity/Stop Bits

No Parity, 1 Stop Bit

O-35

Minimum Response Delay

10mS

O-36

Max Response Delay

5000mS

O-37

Max Inter-Char Delay

25.00mS

O-50

Coasting Select

Logic OR [3]

[0 - 3]

-

5

O-52

DC Brake Select

Logic OR [3]

[0 - 3]

-

5

O-53

Start Select

Logic OR [3]

[0 - 3]

-

5

O-54

Reversing Select

Logic OR [3]

[0 - 3]

-

5

O-55

Setup Select

Logic OR [3]

[0 - 3]

-

5

O-56

Preset Reference Select

Logic OR [3]

[0 - 3]

-

5

BN-70

BACnet Device Instance

1

[1-4194304]

-

BN-72

MS/TP Max Masters

127

[1-127]

-

BN-73

MS/TP Max Info Frames

BN-74

“I am” Service

Once at powerup [0]

[0-1]

-

BN-75

Initialisation Password

“admin”

String[19]

Table 6.1: BACnet specific parameter list

Please refer to the AF-600 FP Drive Operating Instructions for a comprehensive parameter list or to the AF-600 FP Drive Programming Guide for detailed descriptions
of parameters.

6.2 Parameter Description

6.2.1 O-## Options / Comms

Parameter group for configuring communications and options.

O-01 Control Site

Option:

Function:

The setting in this parameter overrides the settings in par. O-50 Coasting Select to par. O-56 Preset Ref-
erence Select
.

[0] *

Digital and ctrl.word

Control by using both digital input and control word.

[1]

Digital only

Control by using digital inputs only.

[2]

Controlword only

Control by using control word only.

AF-600FP BACnet

33

6