DeviceNet

420

-

DNetIIOEpr:

Expected packet rate for 110 connections. According to DeviceNet specifications you must set here a value
different from 0, otherwise time-out errors will not be reported. It is expressed in msec. According to DeviceNet

specifications, this value is internally multiplied by 4. Used only for LocalBus.

Default value

=

0 ins.

421

-

SlaveMapLow:

Bit mapped double word for slave_id 0 to 31. If a bit is set to 1, the communication with the corresponding

server is enabled. Used only for LocalBus.

422

-

SlaveMapiligh:

Bit mapped double word for slave_id 32 to 63. If a bit is set to 1, the communication with the corresponding

server is enabled. Used only for LocalBus.

430

-

DN#RxPLC:

Valid only for “Predefined Master/Slave Connection Set” (PLC). This is the number of bytes received by the
DGFC from the master. Must be set when a Bricks program is executed. It’s calculated when Bricks program is
not executed (see relative chapters). This parameter is analyzed at power-on only.

431

-

DN#TxPLC:

Valid only for “Predefined Master/Slave Connection Set” (PLC). This is the number of bytes transmitted by the

DGFC to the master. Must be set when a Bricks program is executed. It’s calculated when Bricks program is not

executed (see relative chapters). This parameter is analyzed at power-on only.

Liz.

CONFIGURATION PARAMETERS