3) connect the DGFC to the DeviceNet network, power off and then on the system

ATTENTION:

maximum number of parameters read is 10

ATTENTION:

maximum number of parameters written is 10

ATTENTION:

before starting be sure that the number of parameters received and transmitted matches

on the DGFC and master. Otherwise unpredictable behavior can occur.

3.2.1. Example

Note: Remember that at the number of the drive parameter must be sum of the parameter number +2000Hex

(8192 decimal). For example, the number that you must use for T current ref 1 (torque set point has parameter

number 39) is 8231 decimal (8192

+

39) or in hexadecimal 202711 (2000H +2711). During Internal-to-External

(TE) communication the parameter is exchanged from the DGFC to the drive and during External-to-Internal
(El) communication from the drive to the DGFC. SYN (synchronous parameter) is used for high priority param-
eter of the drive, and ASYN for those parameters identified with the symbol

*

in the drive parameter tables.

-

set DPRAM configuration parameters as follows:

par lOOIESYNO @8230

par 101 JESYN 1 @8695

par l2OIEASYNO @8506

par 121 JEASYN 1 @8507

par 1221E ASYN2 @8247

par ilOEISYNO @8200

parillEISYNi

@8201

par1I2EISYN2 @8289

par 140E1 ASYNO @8314

par 141 EIASYNl @8305

par 142 EIASYN2@ 8302

par 143 EIASYN3 @8248

par 144 El ASYN4 @8572

(Ramp ref 1 parameter number 44)

(Pad 0 parameter number 503)

(Enable drive parameter number 314)

(Start/stop parameter number 315)

(Control word parameter number 55)

(T current lim+ parameter number 8)

(T current lim- parameter number 9)

(Enc 1 position parameter number 197)

(Actual Speed parameter number 122)

(Ramp outp [rpm] parameter number 113)

(Ramp ref [rpm]parameternumber 110)

(Status Word parameter number 56)

(Drive ready parameter number 380)

This means that:

-

the PLC will transmit 5 words

(iQ

bytes) to the drive in the following order and manner:

-

word 0 is synchronous parameter 8230 of the drive

-

word 1 is synchronous parameter 8695 of the drive

-

word 2 is asynchronous parameter 8506 of the drive

-

word 3 is asynchronous parameter 8507 of the drive

-

word 4 is asynchronous parameter 8247 of the drive