Tt7~tt, Bile – GE Industrial Solutions OKCV3000CN DeviceNet User Manual

Page 59

Advertising
background image

DeviceNet

Ni

TT7~TT

Power

lap

I-I

-‘-

Power

Supply

~1~

E

N6

Figure D.4: Single Power Supply, Offset Center Connection

Load limits

Maximum voltage drop on V- and V+

5 volts each

Maximum thick cable trunk line current

8 amps in any section

Maximum thin cable trunk line current

3 amps in any section

Maximum drop line current

0.75 to 3.0 amps*

Voltage range at each node

11 n 25 volts

TNet200

*Maximum drop line current depends upon the length of the drop. See below.

Current limits for drop lines are shown in Table below and described by the following equations:

1= 15/L

where I is

the allowable drop line current in amps and L is the drop length in feet, or:

I=4.57/L

where

I

is the allowable drop line current in amps and L is the drop length in meters.

Maximum Allowable Drop Line Current

Drop Length (feet)

Maximum Allowable Current

1

3

3

3

5

3

7.5

2

10

1.5

15

1

20

0.75

TNet2l 0

APPENDIX D