DeviceNet
Ni
TT7~TT
Power
lap
I-I
-‘-
Power
Supply
~1~
E
N6
Figure D.4: Single Power Supply, Offset Center Connection
Load limits
Maximum voltage drop on V- and V+
5 volts each
Maximum thick cable trunk line current
8 amps in any section
Maximum thin cable trunk line current
3 amps in any section
Maximum drop line current
0.75 to 3.0 amps*
Voltage range at each node
11 n 25 volts
TNet200
*Maximum drop line current depends upon the length of the drop. See below.
Current limits for drop lines are shown in Table below and described by the following equations:
1= 15/L
where I is
the allowable drop line current in amps and L is the drop length in feet, or:
I=4.57/L
where
I
is the allowable drop line current in amps and L is the drop length in meters.
Maximum Allowable Drop Line Current
Drop Length (feet)
Maximum Allowable Current
1
3
3
3
5
3
7.5
2
10
1.5
15
1
20
0.75
TNet2l 0
APPENDIX D