User Manual SG Series 400 & 500 UL S2

SG Series S2 500

UPS Model

UPS series number

UPS nominal rating (kVA)

Battery level LED

All lightning lit LED open indicate a battery autonomy of 100%.

LED A

Fixed:

indicates a battery autonomy between 6% and 25%.

Blinking:

indicates a battery autonomy ≤5%.

LED A, B

Indicate a battery autonomy between 26% and 50%.

LED A, B, C

Indicate a battery autonomy between 51% and 99%.

Min:

Battery autonomy time in minutes estimates with actual load.

Load level LED

All LED Off indicate a load status at ≤25%.
LED A

Indicates a load level between 26% and 50%.

LED A, B

Indicate a load level between 51% and 75%.

LED A, B, C

Indicate a load level between 76% and 100%.

LED A, B, C, D

Indicate a load level between 101% and 124%.

LED D blinking

Indicates a load level ≥125%.

Fig. 6.1-2 LEDs on Synoptic Diagram

LEDs on Synoptic Diagram

LED 1

Utility Rectifier OK

LED 2 Utility

Bypass

OK

LED 3 Rectifier

ON

LED 4a Discharging

Battery

LED 4b Charging

Battery

LED 5 Inverter

available

LED 6 Inverter

ON

LED 7

Q1 closed (load on UPS)

LED 8 Automatic

Bypass

ON

LED 9

Manual Bypass Q2 ON

LED 10

Load on UPS

Examples of typical scenarios in the Synoptic Diagram:

Load supplied by Inverter

Load supplied by Automatic Bypass

Load supplied by Battery

Load supplied by eBoost™ Operation Mode (option)

When the Load is supplied by eBoost™ Operation Mode

the “eBoost” text is displayed.