GE Industrial Solutions SG Series 400 & 500 Operating Manual User Manual

Page 32

Advertising
background image

Modifications reserved

Page 32/79

OPM_SGS_USM_M40_M50_2US_V010.doc

User Manual SG Series 400 & 500 UL S2

Code

Alarms

Meaning

4570

OVERLOAD

The UPS-System is in an overload condition >125% on
Inverter, or >150% on Utility.
With Utility unavailable, a sequence of “stop operation”
starts.
Time out depends on Load quantity.

4571

OVERLOAD: LOAD ON UTILITY

With Utility Bypass supply available and load >115%, the
Load is transferred on Utility.
Load will be transferred again automatically on Inverter
when Load <100%.

4581

INVERTER AND UTILITY NOT

SYNCHRONIZED

The voltages of Utility and Inverter are not synchronized,
which causes the opening of K6.

4608

ECO CONFIG FAILURE

The propagation of the eBoost / IEMi configuration to other
units in a Parallel System failed.

4697

BATTERY OVERTEMPERATURE

Detection of Battery over temperature condition.
Can be deactivated by Service Center.

4698

BATTERY POWER INSUFFICIENT

In case of Utility Failure, with the actual Load, the run time
would be below stop operation time (default 3 minutes).

4700

DC LOW

Battery voltage is at the lowest limit.
Will stay Off Inverter until the battery voltage reaches the
value in parameter.

4701

POWER SUPPLY BOARD

FAILURE

Failure detection on the +24V derived from the DC-link
voltage
.

4900

LOAD LOCKED ON INVERTER

The Load is locked on Inverter after 3 Load transfers within
30 seconds.
After time out (default 30 seconds) Bypass will be free.

4955

OVERTEMPERATURE

An over-temperature condition has been detected on
Inverter.
Elapsed “stop operation” time, Inverter shutdown.
With Utility OK, Load is transferred on Utility.

4998

LOAD OFF DUE TO EXTENTED

OVERLOAD

Load Off after time-out of “stop operation” for overload on
Inverter or Bypass (time depending on the % of overload).

4999

LOAD OFF DUE

TO LOW BATT. OR TEMP.

Load Off after time-out of “stop operation” with missing
Utility due to Battery low voltage or over-temperature
condition.