GE Industrial Solutions SG Series 400 & 500 Operating Manual User Manual

Page 27

Advertising
background image

Modifications reserved

Page 27/79

OPM_SGS_USM_M40_M50_2US_V010.doc

User Manual SG Series 400 & 500 UL S2

`

Home\Meter

COUNTERS

Bypass utility failure

:

25

Rectifier utility failure

:

14

Overloads :

15

InvOperTime [h]

:

2135

UPSOperTime [h]

:

3125

eBoost OperTime [h]

:

1379

Statistics screen


The total number of bypass utility faults (bypass utility out

of tolerance).

The total number of rectifier utility faults (rectifier utility out
of tolerance).

The total number of detected output overloads.

The total operating time for the Inverter (in hours).

The total operating time for the UPS (in hours).

The total operating time for the UPS in eBoost™ Operation

Mode (in hours).

This counter is displayed only when eBoost™ Operation
Mode
is available (option).







`

Home\Meter

BATTERY DISCHARGE COUNTERS

Residual Charge Level

100-81% 81-51% 50-21% 20-0%

15 7 3 1

On Battery Time [h]: 15

Statistics battery discharge screen

Residual Charge Level
The number of discharges combined with the percentage
of the available residual battery capacity at the time utility
power is restored.



On Battery Time [h]
The total operating time of the UPS on battery (in hours).







`

Home\Meter

UTILITY

NUMBER OF FAST TRANSIENTS

<2ms >2ms >5ms

>10ms

25

20

7

5

eBoost rate

=

70 %

eBoost™ Operation Mode statistic screen

This screen is displayed only when eBoost™ Operation
Mode
is available.

The number of fast transients occurred on the bypass utility
on the last seven days.

The statistic evaluation in % (100= good; 0= bad) of the
utility, for the eBoost™ Operation Mode.