User Manual SG Series 400 & 500 UL S2

`

Configuration

BATTERY CONFIGURATION

Type :

Lead Acid

Float voltage

:

545 V

Recharge current

:

050.0 A

Autonomy time

:

012 min

Stop Operation time

:

003 min

Capacity :

0250

Ah Cells :

240

ESC



BATTERY CONFIGURATION screen

Recharge type

Recharge type (Lead Acid / NiCd / Boost).

Lead Acid

for:

Sealed battery (VRLA), NiCd without boost-
charge and open battery without boost-

charge.

NiCd

for:

Nickel Cadmium battery with boost-charge.

Boost

for:

O

pen battery with boost-charge.

Float voltage
Voltage to maintain battery charging.

Float voltage = Number of battery cells x battery float voltage per cell.

Typical battery float voltage per cell (ask the battery manufacturer for confirmation):

Sealed battery (VRLA):

2.27Vdc for cell

240 cells x 2.27Vdc = 545Vdc

NiCd without boost-charge:

1.41Vdc for cell

386 cells x 1.41Vdc = 545Vdc

NiCd with boost-charge:

1.41 (1.55 boost-charge) Vdc for cell

351 cells x 1.41Vdc = 495 (545) Vdc

Open battery without boost-charge:

2.23Vdc for cell

240 cells x 2.23Vdc = 535Vdc

Open battery with boost-charge:

2.23 (2.35 boost-charge) Vdc for cell

232 cells x 2.23Vdc = 518 (545) Vdc

Recharge current

Maximum battery recharge current.
Max 20% of battery capacity (Ah).

Example: 250Ah - max recharging current 50A.

Autonomy time

The autonomy time of the battery.
UPS autonomy on battery mode at full load condition.
This value is calculated based on the battery type, capacity and number of cells.

Stop Operation time
Residual battery autonomy time before UPS forced shutdown.
Standard set 3 minutes. Settable from 1 minute to autonomy time in minutes (see tables).

Capacity
Ah capacity of the battery.

Cells
Number of cells of the battery, see “Float voltage”.

Example: 240 battery cells

40 blocks / 12Vdc battery

80 blocks / 6Vdc battery

240 blocks / 2Vdc battery

NOTE !

The values indicated above, must be considered as standard values.
The actual programmed values must be the ones defined from the battery manufacturer.

`

Configuration

CONFIGURATION

Save and exit ?

Yes

CONFIGURATION screen

Screen to save the configuration of set parameters.


Any additional modification of setup parameters can be done

only from a GE SERVICE PERSON as it requires an access code.

Continue