Code

Alarms

Meaning

4309

DRIVER FAILURE

An abnormal condition has been detected on one or more
power modules of the Inverter (temperature or over
current).
Inverter shutdown and cannot be started as long as the
alarm is present.

4312

INV. VOLTAGE OUT OF

TOLERANCE

Inverter Output Voltage is out of the tolerances (± 10%).
Inverter is switched OFF.

4320

ISMAX DETECTION

Detection of Inverter Bridge (Is) current limit causing the
Inverter OFF and possible automatic restart.
After 3 times the Inverter switches-Off, and it can be
restarted manually.

4321

HIGH CURRENT SHARING

A high exchange current value is detected between the
UPS of the parallel system.

4340

INVERTER CONTROL FAILURE

The “Slave” oscillator is not in synchronized with the
Master; thus causing the shutdown of it’s Inverter.
If after a restart the condition remains, the LED inside the
Inverter symbol on the panel will not light up, indicating
that this Inverter cannot supply the Load anymore.

4400

BYPASS FUSE FAILURE

Either one or all the fuses in bypass line have blown.

4404

K6 CLOSING FAILURE

K6 open despite a closing command being issued.
Signaled by auxiliary contact.
The Load cannot be supplied by Automatic Bypass.

4405

K6 OPENING FAILURE

K6 closed despite an opening command being issued.
Signaled by auxiliary contact.

4406

SSM FAILURE

A faulty current has been detected in the static-switch
causing the opening of the contactor K6 for 10 seconds.
After 3 times K6 remains definitively open.
The alarm reset can be done only from Service Center.

4407

SSM OVERTEMPERATURE

Temperature sensor indicates an over temperature on the
Static-Switch.

4410

BYPASS UTILITY OUT

OF TOLERANCE

The Utility Bypass Voltage is out of the tolerances (± 10%).
K6 opens, synchronization with Utility is inhibited and
transfer to Utility is blocked.

4520

NO INVERTER POWER

The Load supplied by Utility exceeds the Inverter power.
The Load remains supplied by Utility until the alarm stays
ON.

4522

FAN FAILURE

A malfunction on the UPS ventilation system was detected.
No change for UPS operation.
Call immediately Service Center for intervention.

4530

LOAD LOCKED ON UTILITY

Load is locked on Utility because 3 transfers on Utility have
been detected in a short time (default 30 seconds).
The transfer will be free after a time defined in parameter
(default 30 seconds).

4531

LOAD ON UTILITY BY ERROR

DETECTOR

Load is transferred to Utility because the error detector
detected a disturbance on the output voltage.

4563

EMERGENCY OFF ACTIVATED

Alarm after detection of an EPO from an external safety
device connected on Customer Interface Board.
Consequently K4, K6, K7 open, Rectifier, Inverter and SSM
are switched Off.