GE Industrial Solutions SG Series 400 & 500 Operating Manual User Manual

Page 62

Advertising
background image

Modifications reserved

Page 62/79

OPM_SGS_USM_M40_M50_2US_V010.doc

User Manual SG Series 400 & 500 UL S2

3. Open the UPS Output Switch Q1 (Pos. O) and then press the Load Off key on all Units.

The Load is now supplied only through the Manual Bypass Q2 of all Units.

LED 8 (Automatic Bypass ON) turns OFF and LED 9 (Manual Bypass Q2 ON) stays lit.

All Rectifiers are shutdown and all output and input Contactors are opened.

The Synoptic Diagram, on all UPS units, must display the status LOAD SUPPLIED BY MANUAL BYPASS Q2.

Synoptic Diagram of first unit

Synoptic Diagram of other units

4. Disconnect the Battery from on all Units by opening (Pos. O) the External Battery Switch or

Fuses.

Wait 5 minutes for DC-Link Capacitors discharge.

The Load is now powered from the Utility through all Manual Bypass Q2 (option) of the Parallel
System
.

END OF PROCEDURE





WARNING!

It will take a minimum of 5 minutes for the DC capacitors to discharge.
Open only the front door, do not open any other part of the UPS.