1 IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important instructions for models SG Series 400 & 500 that should be followed
during installation and maintenance of the UPS and battery.

GENERAL

- Move the UPS in an upright position in its original package to the final destination room.

To lift the cabinets, use a forklift or lifting belts with spreader bars.

- Check for sufficient floor and elevator loading capacity.

- Check the integrity of the UPS equipment carefully.

If you notice visible damage, do not install or start the UPS.

Contact the nearest Service Center immediately.

- WARNING!

RISK OF ELECTRICAL SHOCK:

Do not remove covers, there are no user serviceable parts inside.

- After switching off takes 5 minutes for the DC capacitors to discharge because a lethally high voltage

remains at the terminals of the electrolytic capacitors.

- All maintenance and service work should be performed by qualified service personnel.

The UPS contains its own energy source (battery).

- The field-wiring outlets may be electrically live, even when the UPS is disconnected from the utility.

- Dangerous voltages may be present during battery operation.

- The battery must be disconnected during maintenance or service work.

- This UPS contains potentially hazardous voltages.

- Be aware that the inverter can restart automatically after the utility voltage is restored.

INSTALLATION

- This UPS must be installed and connected only by trained personnel.

- Verify accurately during Commissioning and Maintenance of the UPS, for the following:

Damaged components, squeezed wires and cables, or not correctly inserted plugs.

- After removing the sidewalls of the UPS, make sure that all earth connections when reassembling, are

correctly reattached.

- This UPS is intended for use in a controlled indoor environment free of conductive contaminants and

protected against animals intrusion.

- WARNING! HIGH EARTH LEAKAGE CURRENT:

Earth connection is essential before connecting to AC input!

- Switching OFF the unit does not isolate the UPS from the utility.

- Do not install the UPS in an excessively humid environment or near water.

- Avoid spilling liquids on or dropping any foreign object into the UPS.

- The unit must be placed in a sufficiently ventilated area; the ambient temperature should not exceed 104°F (40°C).

- Optimal battery life is obtained if the ambient temperature does not exceed 77°F (25°C).

- It is important that air can move freely around and through the unit. Do not block the air vents.

- Avoid locations in direct sunlight or near heat sources.

STORAGE

-

Store the UPS in a dry location; storage temperature must be within -13°F (-25°C) to 131°F (+55°C).

-

The optimal temperature for Battery storage is 68°F (20°C) to 77°F (25°C) and shall never exceed the range -

4°F (-20°C) to 104°F (40°C).

- If the unit is stored for a period exceeding 3 months, the battery must be recharged periodically (time

depending on storage temperature).

BATTERY

- The battery-voltage is dangerous for person’s safety.

-

When replacing the battery, use the same cells number, voltage (V), capacity (Ah).

All the battery used, shall be of the same manufacturer and date of production.

- Proper disposal or recycling of the battery is required.

Refer to your local codes for disposal requirements.

- Never dispose of battery in a fire: they may explode.

- Do not open or mutilate battery: their contents (electrolyte) may be extremely toxic.

If exposed to electrolyte, wash immediately with plenty of water.

- Avoid charging in a sealed container.

- Never short-circuit the batteries.

When working with batteries, remove watches, rings or other metal objects, and only use insulated tools.

- In case of air shipment, the cables +/- going to the battery fuses/terminals shall be disconnected and isolated.