User Manual SG Series 400 & 500 UL S2

7.2 PROCEDURES FOR SG Series 400 & 500 PARALLEL SYSTEM AND PARALLEL

SYSTEM WITH COMMON BATTERY

7.2.1 SG Series 400 & 500 Parallel System start-up

WARNING !

Before proceeding to Turn ON the UPS System, ensure that the AC and DC external
isolators are OFF (Pos. O), and prevent their inadverted operation.
Ensure that the output load distribution can be powered and all the output isolators
are open (Pos. O).

Open the front door on all UPS units and make sure that:

All the connections to the input/output bus bars of the UPS have been made correctly.

The safety screens are fixed in their position.

The UPS Output Switch Q1, Manual Bypass Switch Q2 (option) and the External Battery Switch or
Fuses
must be open (Pos. O).

LEDs on Synoptic Diagram

S

G

S

_

400

-50

0_S

2

_S

w

itc

hes

Q1-Q

2_01

Q1

0 OFF

I ON

Q2

0 OFF

I ON

Q1 UPS Output Switch

Q2 Manual Bypass switch (option)

LED 1

Utility Rectifier OK

LED 2

Utility Bypass OK

LED 3

Rectifier ON

LED 4a Discharging Battery

LED 4b Charging Battery
LED 5

Inverter available

LED 6

Inverter ON

LED 7

Q1 closed

LED 8

Automatic Bypass ON

LED 9

Manual Bypass Q2 ON (option)

LED 10

Load on UPS

Key Key Key LED LED LED

Inverter ON

Inverter OFF

Load Off

Stop Operation

Alarm

Operation


1. Switch-ON the Utility Voltage, on all UPS units, from the input distribution (both rectifier and

bypass if separated).

At this stage the electronic power supply is switched ON.

Overall test results

Test1 OK

Test7 OK

Test2 OK

Test8 OK

Test3 OK

Test9 OK

Test4 OK

Test10 OK

Test5 OK

Test11 OK

Test6 OK

The UPS performs a SELFTEST.

A successful termination of the tests will be indicated with Overall
test results “OK”.
Commissioning cannot be continued should one or more tests

result to be negative.
Please contact in this case your Service Center.

With “Overall test results - OK” the Synoptic Diagram is displayed.

LED 1 (Utility Rectifier OK) and LED 2 (Utility Bypass OK) must be ON.

The buzzer sounds, press the “MUTE” key to reset acoustical alarm. LED Alarm remains lit.