5 commands, Commands – GE Industrial Solutions SG Series 400 & 500 Operating Manual User Manual

Page 43

Advertising
background image

Modifications reserved

Page 43/79

OPM_SGS_USM_M40_M50_2US_V010.doc

User Manual SG Series 400 & 500 UL S2

6.5 COMMANDS

The COMMANDS mode is entered any time the “CMDS” button is pressed.

Allows the user to execute UPS operation commands.

In this mode the buttons perform the following functions:

Return to HOME screen.

Scrolls forward to the next screen.

V

Scrolls forward to the next line.



Confirm the selection made.

It is possible to view any pushbutton functional description by pushing the button for more than 3
seconds.

`

Home\Commands

COMMANDS

LAMP TEST

INVERTER

ON

INVERTER

OFF

RECTIFIER

ON


V



Commands screen 1

LAMP TEST
Signaling LEDs test and buzzer test (all LED should be lit and
blinking and the acoustical alarm should be activated).

INVERTER ON

Command to switch the inverter.

INVERTER OFF

Command to shutdown the inverter.

RECTIFIER ON

Command to switch the rectifier.
Only for Service Center, the command
access is protected by a code.

NOTE !

When eBoost™ Operation Mode is enabled, control of Inverter status and selection
of the feed path is done autonomously by the UPS control logic.
Therefore, Inverter ON / Inverter OFF commands are disabled when eBoost™
Operation Mode
is enabled.


`

Home\ Commands

COMMANDS

RESET TOTAL OFF

REQUEST

TOTAL

OFF

V



Commands screen 2

RESET TOTAL OFF
Reset Total OFF command should be executed to switch ON
UPS after a “Load Off” operation.

REQUEST TOTAL OFF
Command “Load Off”.

Screen sequence to execute the command

Load

Off”:

`

Home\Commands

`

Home\Commands

COMMANDS COMMANDS

RESET TOTAL OFF

RESET TOTAL OFF

REQUEST TOTAL OFF

CANCEL TOTAL OFF

EXECUTE TOTAL OFF

V



V



As the command procedure

of “Load Off” is finished the
“REQUEST TOTAL OFF”

screen appears again.