User Manual SG Series 400 & 500 UL S2

`

Home\Meter

INVERTER

f 60

Hz

L1 277

V

L2 277

V

L3 277

V

T +25°

C

SYNCHRONIZED

Inverter data screen

f

The output frequency of the Inverter.

L1

L2

3-phase output voltage PHASE/NEUTRAL.

L3

T

The temperature of the inverter bridge.

The synchronization status of the inverter with respect to

utility (SYNCHRONIZED / NOT SYNCHRONIZED).

`

Home\Meter

SYSTEM LOAD

L1 :

277 V

301.0 A

50 %

L2 :

277 V

241.0 A

40 %

L3 :

277 V

181.0 A

30 %

LOAD ON INVERTER

Load on phases screen 1

… V

Output voltage PHASE/NEUTRAL for each phase.

… A

The output current as RMS values (for RPA: total
value of Parallel System).

… %

The output load as percentage (for RPA: with
respect to the rated power of Parallel System).

The source of the power supplied to the load:

- DETOUR ON (Q2 close)

- LOAD ON INVERTER

- Q1 OPEN

- LOAD ON BYPASS

- LOAD OFF

- LOAD ON BYPASS (eBoost)

- ON BATTERY

`

Home\Meter

SYSTEM LOAD

L1 : 75.0 kW

83.3 kVA

PF +/-0.90

L2 : 60.1 kW

66.7 kVA

PF +/-0.90

L3 : 45.0 kW

50.0 kVA

PF +/-0.90

LOAD ON INVERTER

Load on phases screen 2

… kW

The load active power (kW) (for RPA: total value of
Parallel System).

… kVA The load apparent power (kVA) (for RPA: total

value of Parallel System).

… PF

The load power factor:
+ for inductive loads (lagging power factor).
- for capacitive loads (leading power factor).

The source of the power supplied to the load:

- DETOUR ON (Q2 close)

- LOAD ON INVERTER

- Q1 OPEN

- LOAD ON BYPASS

- LOAD OFF

- LOAD ON BYPASS (eBoost)

- ON BATTERY

`

Home\Meter

MODULE LOAD

Total kVA

200 kVA

Percentage 40%

LOAD ON INVERTER

Module load screen

Total kVA
The load level in kVA (for RPA: only this unit).

Percentage
The load level as a percentage of the nominal rated load

(for RPA: only this unit).

The source of the power supplied to the load:
- DETOUR ON (Q2 close)

- LOAD ON INVERTER

- Q1 OPEN

- LOAD ON BYPASS

- LOAD OFF

- LOAD ON BYPASS (eBoost)

- ON BATTERY