3.6 UNPACKING

The UPS and Battery Cabinets may be shipped packaged in carton boxes or in wooden crates (if
requested).

Move the cabinets as close as possible to the final location before removing from the pallet.

If delivered in a wooden crate, remove the cabinet from the pallet with care, because of the heavy
weight of the equipment.

White color

=

without any anomaly

Red color

=

anomaly evidence

Fig. 3.6-1 ShockWatch device

The package of the SG Series 400 & 500 is
equipped with ShockWatch (indicator for shock),
and TiltWatch (indicator for overthrow) on the
outside.

These devices indicate an eventual shock or
overthrow during transport.


Whenever these devices show a possible
anomaly, the UPS shall not be commissioned
before consulting a “Service Center”
.

Fig. 3.6-2 TiltWatch device


NOTE !

Take care not to damage the UPS when moving by forklift.
A damaged UPS must never be installed or connected to Utility
or Battery!
In case of any damage sustained during the transport, immediately inform the
shipping agent!
A detailed report of the damage is necessary for any indemnity claim.