Power connection with dual input utility (option) – GE Industrial Solutions SG Series 400 & 500 Installation Guide User Manual

Page 26

Advertising
background image

3.8.3 Power connection with dual input utility (option)

Position of the PE bolt in case the
cable input is from the bottom of the UPS

PE

SGSU

_400-5

00_S2

_UPS c

onnec

tion se

parate

_GE_0

1US

PE

PE

Typical installation using

common NEMA two hole lugs

PE Input Utility

PE Load

Utility Neutral

Load Neutral

Load

Typical installation using

common NEMA two hole lugs

2

- I

NP

UT

U

TI

LI

TY

B

YP

AS

S

(o

pt

io

n)

L1-2

L3-2

L2-2

L1

L2

L3

L3-1

1 - INPUT UTILITY

RECTIFIER

L1-1
L2-1

+

-

Fig. 3.8.3-1 Power connection with Dual Input Utility (option)


Use 1/2” bolts for the cable connections on INPUT / OUTPUT power wiring Bus Bars.
Cable terminations are to the Rectifier Input / Output Bus Bars as shown above.
Connect wire to the Bus Bars using appropriate tools and appropriate torque.
Torque specification for two hole lugs on Bus Bars: see Section 3.8.1.

Dual Input Configuration Rectifier / Bypass (option)

L1-1

Rectifier Phase A

L1-2

Bypass Phase A

L2-1

Rectifier Phase B

L2-2

Bypass Phase B

L3-1

Rectifier Phase C

L3-2

Bypass Phase C

PE Input Utility

Ground

N - Bypass

Bypass Neutral

For dual input configurations, a neutral conductor is required from the bypass source
only.
Always verify that the received UPS is as per the configuration ordered.
While installing UPS dual source, shorting jumpers BR1
, BR2 and BR3 should not be
present. See Fig. 3.8.3-3
.

Output Load

L1

Load Phase A

L2

Load Phase B

L3

Load Phase C

N

Load Neutral

PE Load

Load Ground

Modifications reserved

Page 26/41

OPM_SGS_ISG_M40_M50_2US_V021.doc

User Manual SG Series 400 & 500 UL S2