9.2-2 Bus connection on terminal units

Terminal units
On the parallel bus PCB P34 – Bus Interface, of the first and last units (terminal) of the parallel
system the Jumpers JP1, JP2, JP3 and JP4 MUST BE INSERTED.


JP2

JP1

JP4

IM 004

8

JP3

JP4

JB

JA

JP3

JB1

JA1

SGSU_400-500_S2_RPA-IM0048_03

JA2

JB2

JP2

JP1

Fig. 3.9.2-3 Bus connection on intermediate units

Intermediate units
On the parallel bus PCB P34 – Bus Interface of the intermediate units of the parallel system the
Jumpers JP1, JP2, JP3 and JP4 MUST BE REMOVED.


NOTE !

In a parallel system composed of 2 or more units, only the first and last units (having
1 input JA
and JB free) have the Jumper JP1, JP2, JP3 and JP4 inserted on parallel
bus PCB “P34 – Bus Interface”
(see Fig. 3.9.2-2).

Modifications reserved

Page 34/41

OPM_SGS_ISG_M40_M50_2US_V021.doc

User Manual SG Series 400 & 500 UL S2