Power Management Control System
Chapter 1 – Introduction

8

IED Name

IED Name

IED Name

IED Name

Function

Communications Protocol (Modbus Speed)

RS-485 Repeater

Communications

Modbus RTU (19.2 Kbaud)

369 Motor Management Relay

Metering/Control

Modbus RTU (19.2 Kbaud)

EPM 7500 Electronic Power Meter

Protection/Control

Modbus RTU (19.2 Kbaud)

EPM 7600 Electronic Power Meter

Protection/Control

Modbus RTU (19.2 Kbaud)

Motor Manager II (MMII)

Protection/Control

Modbus RTU (19.2 Kbaud)

EPM7430D/EPM7450D (Futura)

Protection/Control

Modbus RTU ( 9600 baud)

Spectra Electronic Control Module

Protection

commnet (requires Modbus Concentrator)

Spectra MVT for GEK Frame MCCB

Metering/Protection

commnet (requires Modbus Concentrator)

SR469 Motor Management Relay

Protection/Control

Modbus RTU (19.2 Kbaud on 1 or 2 ports)

SR489 Generator Management Relay

Protection/Control

Modbus RTU (19.2 Kbaud on 1 or 2 ports)

SR745 Transformer Management Relay

Protection/Control

Modbus RTU (19.2 Kbaud on 1 or 2 ports)

SR750 Feeder Management Relay

Protection/Control

Modbus RTU (19.2 Kbaud on 1 or 2 ports)

SR760 Feeder Management Relay

Protection/Control

Modbus RTU (19.2 Kbaud on 1 or 2 ports)

POWER LEADER MDP Overcurrent Relay

Protection

Modbus (19.2 Kbaud) or commnet
(commnet requires Modbus Concentrator)

POWER LEADER Modbus Monitor

Monitoring

Modbus RTU (19.2 Kbaud on 1 or 2 ports)

POWER LEADER Meter

Metering

commnet (requires Modbus Concentrator)

Table 1. IEDs supported by PMCS.

2

2 The POWER LEADER Ethernet Gateway is not listed in Table 1. The Ethernet Gateway is an alternate host for the RS-485 networks used when the

PMCS resides on the Ethernet level.