Power Management Control System
Chapter 2 – Network Design

18

Modbus

Segment A

Monitor

#1

Monitor

#1

Monitor

#1

Monitor

#2

Monitor

#1

Monitor

#2

Example A

Example B

Modbus

Segment A

Modbus

Segment B

Modbus

Segment A

Modbus

Segment A

Modbus

Segment B

Example C

Example D

Figure 14. Valid Modbus Monitor network architectures.

CAUTION:

Any other wiring of the Modbus

Monitor may result in incorrect operation and
errors.

CAUTION DUAL PORT MONITOR USERS: Do
not connect the Monitor’s two RS-485 ports to the same
Modbus segment.

This will cause communication

errors and possibly damage the Monitor.

Example A shows a single Modbus Monitor wired to one
Modbus segment. Example B shows the same monitor in a
dual-port version, wired to two different Modbus segments.

Examples C and D illustrate fully loaded Modbus
segments. No more than two Monitors are permitted on
any Modbus segment.

Example C illustrates a pair of Monitors connected to a
single Modbus segment. In this example, the Monitors
may be either single port or dual-port versions, provided
both are the same version (see note below). Example D
shows the same pair of Monitors wired to a second Modbus
segment.

CAUTION:

With regard to Example C (two

Monitors on a single RS-485 segment), it is not
permissible to mix different models of Monitors
on a segment. Monitors #1 and #2 must be of the
same model, either both single-port or both dual-
port.

The nature of the other network architectures

makes this concern irrelevant for examples A, B,
and D, since in Example A you could have either
a single- or a dual-port Monitor, while in
Examples B and D you may only use a dual-port
monitor(s).