Power Management Control System

Chapter 2 – Network Design

17

RS-485 IEDs

(31 Max)

Host

Modbus

Concentrator

MC

Commnet IEDs

(up to 32 per Modbus Concentrator,

215 total per RS-485 network)

Figure 10. Network illustrating Modbus Rule 6.

7. A single RS-485 network may have no more than

4000 feet of cable (total cable length, not distance
between IEDs). Figure 11 illustrates this rule.

RS-485 IEDs

(31 Max)

Host

Total Cable Length < 4000 feet

100 ft

300 ft

1500 ft

1500 ft

200 ft

300 ft

Figure 11. Network illustrating Modbus Rule 7.

8. RS-485 repeaters may be used to extend the range

beyond 4000 feet. A single RS-485 repeater may be
used to provide a 4000-foot extension, and each
additional repeater in a sequence extends the range
by another 4000 feet. Figure 12 illustrates this rule.

With 2 Repeaters,

Total Cable Length < 8000 feet

Host

100 ft

200 ft

2500 ft

500 ft

700 ft

4000 ft

R

R

RS-485

Repeaters

Figure 12. Network illustrating Modbus Rule 8.

9. There may be no more than two RS-485 repeaters

between any two RS-485 IEDs. Figure 13 illustrates
this rule.

Correct - Maximum two repeaters between RS-485 IEDs

Incorrect - more than 2 repeaters between RS-485 IEDs

Rptr

Rptr

Rptr

Rptr

Rptr

Figure 13. Network illustrating Modbus Rule 9.

NOTE ON DUAL-PORT RS-485 IEDS:
Several of the Multilin power management IEDs
offer two RS-485 ports on the same IED. Do not
connect both RS-485 ports to a PMCS network.

The

same data are available from both RS-485 ports
and will cause conflicts if the PMCS attempts to
access both ports simultaneously.
However, the Modbus Monitor’s wiring scheme is
slightly different from the Multilin scheme. The
dual-port version of the POWER LEADER
Modbus Monitor MUST be connected to two
separate RS-485 networks. See Rule 10 for details.

10. Modbus Monitors (dual-port version) may not be

wired in any configuration other than the four
shown in Figure 14. Although the Monitor’s RS-485
ports have separate addresses, you may NOT wire
the same Modbus network to both ports. A two-port
Modbus Monitor must be wired to two separate
Modbus networks.

NOTE

: For more information on wiring the

POWER LEADER Modbus Monitor, refer to
DEH-027, Modbus Monitor User’s Guide.