Power Management Control System
Chapter 2 – Network Design

34

met, Bill selects Modbus addresses for the IEDs. He checks
Section 2-7 and sees that he can assign the Modbus IEDs
on each network any Modbus address between 1 and 247
(except for the Modbus Concentrator, which must have an
address between 1 and 32). The commnet IEDs must have
Modbus-equivalent addresses between 33 and 247. He
selects addresses and records them for future reference.
The address chart is shown in Table 12.

RS-485

Network #

IED Type

Physical
Location

Modbus
Address

1

Multilin 565

Power intake
area

01

2

Multilin 269+

Assembly line

01

3

SR469 Motor
Management
Relay

Assembly line

01

3

Modbus Monitor
#1, RS-485 Port A

Lathe area

02

3

Multilin 239
Motor Protection
Relay

Machining area

03

3

Modbus Monitor
#2, RS-485 Port A

Machining

04

4

Multilin SR750
Feeder
Management
Relay

Milling area

01

4

EPM 3720

Milling area

02

4

Modbus Monitor
#1, RS-485 Port B

Lathe area

03

4

Modbus Monitor
#2, RS-485 Port B

Machining area

04

4

Modbus
Concentrator

Machining area

05

4

EMVT-C trip unit

Machining area

33

4

Spectra ECM

Machining area

34

4

POWER
LEADER EPM

Machining area

35

Table 12. IED Addresses for Case Five.

Chapter 3 provides Bill with physical wiring requirements
and rules. He’ll use Belden 3074F cable, readily available.
He also locates the correct terminating resistors at both
ends of each RS-485 network.

He installs the IEDs according to the instructions in each
IED’s user manual. He then makes connections to the RS-
485 communications cable in daisy-chain fashion, one IED

to the next, terminated at both ends of each RS-485
network, double-checking his wiring against the example
provided in Section 2–4. Since several of his Multilin IEDs
have two ports, he is careful to connect only one RS-485
port per IED. The Modbus Monitors are also RS-485 dual-
port, but Bill carefully follows the wiring instructions to
correctly connect them to the RS-485 networks. The A port
of each Monitor is connected to one RS-485 network and
the B port of each is connected to another network.

He must also bear in mind proper shield-grounding
considerations: each RS-485 IED grounded at only one
point and no two IEDs’ grounds connected (Rule 4,
Section 2-4). The Multilin 565 special grounding
considerations are also taken into account (see Chapters 2
and 3).

Bill assigns a Modbus address to each IED. He then sets
communication speeds and functional and protective
parameters according to the instructions in each user
manual.

Bill installs the PMCS software at the host PC and
configures IED addresses at the host to match the
addresses assigned to each IED on the network.

Configuration files for the Modbus Monitors are
downloaded to the units or created using the Monitor’s
“Create from PMCS” feature (see DEH-027 for details).

When all connections have been made and the IEDs and
software are appropriately configured, Bill applies power
to the system and runs tests to assure that everything is
functioning properly.

If any difficulties are encountered, Bill refers to the
trouble-shooting guide in Chapter 4.