Power Management Control System

Appendix A – IED Descriptions

53

All voltage, current, power, and energy readings are
true RMS, including harmonics. Energy readings
provide bi-directional (import/export) indication.

No potential transformers (PTs) are required on the
voltage inputs for systems up to 347 Vac line-to-
neutral/600 Vac line-to-line. For higher voltage systems,
PTs with 120 Vac secondaries may be used. The
transformer-coupled current inputs provide 300 A surge
protection and accept CTs with 5 A full-scale outputs.

Electronic Power Meter EPM 3720

The Electronic Power Meter 3720 offers the same
capabilities as the EPM 3710, plus many additional
measurements and more advanced features, including
the following:

Three-phase voltage inputs

Three-phase current inputs

Neutral/ground current input

Three relay outputs

Four digital inputs with pulse-counter on all four
inputs with maximum pulse count frequency of
10 Hz

One analog voltage input, one analog current
output

729 measured parameters, including harmonic
distortion and demand

Waveform-capture triggering communications
port or setpoint

Waveform-recording triggering communications
port or setpoint

Eight programmable trend logs, 12 parameters
each, 11,520 record capacity (40 days), triggered
by time interval or setpoint

Event log with 100 records standard, resolution
one second

Minimum/maximum logs: one preset with over
100 parameters; 16 programmable logs of 16
parameters each with a trigger parameter for
each log

17 setpoints: 11 standard-speed, six high-speed;
trigger event log, relay control, snapshot log,
waveform capture or waveform recorder

The Electronic Power Meter 3720 provides hundreds of
high-accuracy real-time measured parameters, as well as
minima, maxima, and status parameters.

All voltage, current, power, and energy readings are
true RMS and sensitive to beyond the 50

th

harmonic.

Four-quadrant readings measure bidirectional

(import/export) energy flow, useful in any
cogeneration application.

No PTs are required on the voltage inputs for systems
up to 347 Vac line-to-neutral and 600 Vac line-to-line.
For higher-voltage systems, PTs with 120 Vac
secondaries may be used. The transformer-coupled
current inputs provide 300 A surge protection and
accept CTs with 5 A full-scale outputs.

Electronic Power Meter EPM 7300

The Electronic Power Meter 7300 provides over 100
high-accuracy, three-phase measurements. Its compact
size, simple installation and high reliability make it
ideal for use in panelboards, switchboards, switchgear,
gensets and UPS systems. With RS-485 communications,
it can be integrated into a power management system
such as PMCS.

Instantaneous Measurements

Voltage (l-l/l-n), per phase and average

Current, per phase and average

Real Power, per phase and total

Reactive Power, per phase and total

Apparent Power, per phase and total

Power Factor, (lead/lag), per phase and total

Voltage Unbalance

Current Unbalance

Frequency

Energy

Imported, exported, absolute and net kWh &
kVARh. Accumulated kVAh

Demand

Sliding Window, Predicted, and Thermal
Demand on kW, kVAR, kVA, and I average

Minimums and Maximums

Voltage (l-l/l-n) per phase

Current per phase

kW, kVAR, kVA, Power Factor, Frequency

Sliding Window Demand for kW and kVA

Electronic Power Meter EPM 7500/7600/7700

The EPM 7500/7600/7700 is a highly advanced digital
power meter, suited to virtually any power monitoring
and control application. This Intelligent Electronic
Device (IED) can take the place of numerous
transducers, meters and control circuits in a power
monitoring system. The EPM 7700 provides true RMS