Connect tech rs-485 card, Ethernet gateway – GE Industrial Solutions POWER LEADER PMCS Network Architecture Guide User Manual

Page 77

Advertising
background image

Power Management Control System

Appendix C – Special Wiring Considerations

67

NOTE: The RTU port ground signal connection
is not required but may be connected if needed.
A one- to two-foot length should be enough for
the four-wire RTU cable (with 25-pin female and
15-pin male D connectors) between the PLC and
the 2/4 wire converter. Only Port 2 can be used
for RTU communication on the 28-point Micro
90.

Connect Tech RS-485 card

For this connection, you’ll need a length of Belden 9271
cable covered with sleeving and a female DB-9 connector.

The DB-9 connector should have the following jumper
connections made inside the connector.

Pin 1 to Pin 2

Pin 3 to Pin 4

Pin 6 to Pin 7

Pin 8 to Pin 9

Connect the cable to the DB-9 connector as follows:

Conductor

DB-9 Pin

Cable 1

White

1

Blue

3

Shield

Metal shell

Apply heat-shrink tape or jacket over the connector for
protection.

At the end opposite the connector, strip about 3 inches off
the outer jacket of the cable.

Ethernet Gateway

The Ethernet Gateway RS-485 connection requires one
48-inch length of Belden 9271 cable covered with sleeving
and a male DB-9 connector.

Connect one end of the cable to the DB-9 connector as
follows:

Conductor

DB-9 Pin

White

1

Blue

2

Shield

5

Apply heat-shrink tape or jacket over the connector for
protection.

At the end opposite the connector, strip about 3 inches off
the outer jacket of the cable.