2–5 modbus wiring rules – diagrams – GE Industrial Solutions POWER LEADER PMCS Network Architecture Guide User Manual

Page 25

Advertising
background image

Power Management Control System

Chapter 2 – Network Design

15

2–5 Modbus Wiring Rules – Diagrams

The Modbus network protocol has wiring rules and limits
on the number of IEDs that may be attached.

This section describes in greater detail the rules you must
follow when designing a Modbus network.

WARNING:

Network wiring and grounding

rules described herein apply primarily to
commercial/industrial installations. Substation
installations will exist in the presence of
dangerously elevated ground potential relative to
points outside of the station grid as well as large
electromagnetic induction fields. Additionally,
large ground faults can elevate substation
ground potentials. Follow local utility best-
practices/safety procedures to prevent

risk of

shock/electrocution to personnel and damage to

equipment that could result in a loss of
protection and communications.

NOTE:

It is important to take future

expandability into consideration when designing
a network configuration. This is particularly so
when the network is near its maximum number
of IEDs or maximum cable length. Adding IEDs
to a network after it has been installed may
require rewiring the network.

CAUTION:

Wire-run distances mentioned in the

configuration rules assume application above
grade or in conduit. For below-grade
applications, refer to Section 3–1, Wiring
Requirements.

Regardless of which platform is supporting the RS-485
networks (Ethernet Gateway, RS-485 card, or RS-232/RS-
485 converter), the following rules apply to each
individual RS-485 network.

1. Each RS-485 network may support up to 31 Modbus

IEDs. Figure 7 illustrates this rule. (See the
exception below Figure 6.)

31 RS-485 IEDs maximum;

PMCS Host PC, Ethernet Gateway or MSP

always located at one end of Modbus network.

Host

Figure 7. Network illustrating Modbus Rules 1 and 2.

Exception to Rule 1: Some types of IEDs must be
wired on dedicated private serial network segments,
one IED per serial Modbus line.

2. The host (or Ethernet Gateway) must always be

located at one end of any Modbus segment. It may
not be located in the center of a Modbus network.
Figure 7 shows the correct placement of the host
(PC or Ethernet Gateway).

3. All Modbus IEDs on a single RS-485 network must

communicate at the same baud rate. If IEDs with
different communication speeds are connected to
the same RS-485 network, the whole segment will
communicate at the speed of the slowest IED. Figure
8 i
llustrates this rule. (Communication speeds for
supported IEDs are listed in Table 1.)

Figure 8. Network illustrating Modbus Rule 3.

4. Each RS-485 network must be properly terminated

at both ends of the cable run after the final IED.
(See Section 3–1 for details on termination.) Figure
9 i
llustrates this rule.

Advertising