Sr760 feeder management relay, Motor manager ii (mmii) – GE Industrial Solutions POWER LEADER PMCS Network Architecture Guide User Manual

Page 71

Advertising
background image

Power Management Control System

Appendix A – IED Descriptions

61

protection for time-overcurrent, hi-set overcurrent, lo-set
overcurrent, and directional control. Overvoltage,
undervoltage, and underfrequency functions each have
two independent stages. With 14 programmable logic
inputs and seven outputs, the SR750 can be easily
configured for specific applications. The relay has
extensive monitoring and metering functions. It has an
internal memory that allows it to record the last 100
events, the last 10 faults, and a total of 256 cycles of
oscillography data. The relay performs self-tests in the
background during operation. A simulation function
allows you to test the relay without the need for external
ac voltage and current inputs.

The relay has a two-line display and keypad, as well as
three serial ports for computer interface.

Application

Industrial and utility feeders

Protection and Control

Complete time overcurrent

Complete instantaneous overcurrent

Directional overcurrent control

Undervoltage and overvoltage

Negative-sequence voltage

Undervoltage automatic restoration

Bus underfrequency

Underfrequency automatic restoration

Breaker failure

Manual close control

Cold-load pickup control

Four setting groups

Syncrocheck - V, f, Hz, & dead-source

14 programmable logic inputs

Bus transfer

Monitoring and Metering

Fault locator, record of last 10 faults

Breaker operation & trip failure

VT Failure

Power factor – two independent stages

Analog input – level and rate

Total breaker arcing current

Event recorder – Last 100 events

Oscillography – 256 cycles

Metering: V, I, Hz, var, VA, PF

Demand: I

0

, I

0

, I

0

, MW, Mvar, MVA

Data Logger

User Interface

40-character display and 24 LEDs

Full numeric keypad

RS-232 and RS-485 ports

SR760 Feeder Management Relay

The Multilin SR760 Feeder Management Relay is an
enhanced version of the Multilin SR750 relay, adding a
four-shot recloser.

EPM7430D/EPM7450D

The Futura+ multifunction digital power-monitoring
system offers the most extensive monitoring and
analysis available. Surpassing all other meters in its
class, this unit fulfills all your metering, data recording
and power analysis needs. This is simply the best power
monitoring and analysis solution ever. For a graphical
view of all the meter can do, check out the Futura+
Communicator link. You will be very impressed.
Features

Multifunction Power Monitoring, Measuring
Every Parameter of Electrical Power

True RMS with 0.15% Accuracy

Extensive On-Board Storage for Virtually
Unlimited Data Trending

100 High-Speed Captured Waveform Events for
Voltage and Current Surges and Sags (All 6
Channels, 60 Cycles Per Channel Constitute an
Event)

Dual Digital Communication Ports: Modbus
RTU/ASCII, DNP 3.0, Modbus+ and Ethernet
TCP/IP

Harmonic Distortion to the 31st Order

Multiple and Remote Displays

Extensive Digital and Analog I/O Capabilities
and Storage

Motor Manager II (MMII)

The Motor Manager 2 (MM2) combines control
functions and comprehensive motor protection in one
package. This compact device provides sophisticated
control and protective relaying at significant cost
savings over the discrete devices normally found in a
low voltage motor control center (MCC). One MM2 is
required for every starter in the MCC. The contactor
can be energized and de-energized using the MM2’s
direct wired inputs, or via the serial port. A total of 6
fixed and 10 programmable switch inputs are available.
A wide range of starter types may be controlled by the
MM2 using two contactor outputs and two auxiliary

Advertising