Table 8. ied addresses for case one, Plc 90/30, Epm 3720 – GE Industrial Solutions POWER LEADER PMCS Network Architecture Guide User Manual

Page 36: Multilin 269, Multilin 565, Ied type physical location modbus address, Assembly line 01, Milling 02, Lathe area 03, Machining 04

Advertising
background image

Power Management Control System
Chapter 2 – Network Design

26

Bill's Office

GHO Corp Machine Shop -

network wiring diagram

350'

550'

200'

300'

Terminating

Resistors

Multilin 565
Feeder Management Relay

PLC 90/30
Programmable Logic Controller

EPM 3720
Electronic Power Meter

EPM 3720
Electronic Power Meter

EPM 3720
Electronic Power Meter

Multilin 269+
Motor Relay

350'

550'

Main power feed

Assembly Line Area

Milling Area

Machining Area

Lathe Area

Figure 22. Floor layout for Case One.

Bill’s calculates his total cable length at 2300 feet, well
short of the 4000-foot limit.

Next, Bill checks Table 2 for the Modbus wiring rules.

Proper termination is required at each end of the network,
and is provided at the RS-485 card by attaching jumpers to
the correct pins (see RS-485 card user manual). The
appropriate terminating resistors must be used at the
opposite end of each RS-485 network, per Section 2–4, rule
3.

His cable length is well under the 4000-foot limit, so no
repeaters will be needed.

Because he has only six IEDs to connect, only one RS-485
network is required, and thus an RS-232/RS-485 converter
would do the job. However, he considers the performance
recommendations given in Section 2-6 and, remembering
his earlier note about the different baud rates of his
Modbus IEDs, he decides to distribute the IEDs across four
ports of an RS-485 network card, so that he can place IEDs
with matching baud rates on the same RS-485 network.

The system redesigned for optimum performance is shown
in Figure 23.

Bill's Office

GHO Corp Machine Shop -
network wiring diagram

350'

550'

100'

Terminating
Resistors

Multilin 565
Feeder Management Relay
at main power feed

PLC 90/30
Programmable Logic Controller

EPM 3720
Electronic Power Meter

EPM 3720
Electronic Power Meter

EPM 3720
Electronic Power Meter

Multilin 269+
Motor Relay

600'

600'

Assembly Line Area

Milling Area

Machining Area

Lathe Area

Network 4 - 19.2 kbaud

Network 3 - 19.2 kbaud

N

et

w

or

k

2

- 2

40

0

ba

ud

N

et

w

or

k

1

- 9

60

0

ba

ud

RS485 networks
terminated at host PC

Figure 23. Redesigned layout for Case One.

Confident that his new design will provide maximum
performance, and with his wiring requirements and limits
met, Bill moves on to select Modbus addresses for the IEDs.
He checks Section 2-7 and sees that he can assign his IEDs
any Modbus address between 1 and 247. He selects
addresses and records them for future reference. The
address chart is shown in Table 8.

IED Type

Physical Location

Modbus Address

PLC 90/30

Assembly line

01

EPM 3720

Milling

02

EPM 3720

Lathe area

03

EPM 3720

Machining

04

Multilin 269+

Assembly line

05

Multilin 565

Power intake area

06

Table 8. IED Addresses for Case One.

Chapter 3 provides Bill with physical wiring requirements
and rules. He finds that he’ll have to use Belden 3074F
cable, readily available. He also locates the correct
terminating resistors at both ends of each RS-485 network.

He installs the IEDs according to the instructions in the
user manual for each IED. He then makes connections to
the RS-485 communications cable in daisy-chain fashion,
one IED to the next, terminated at each end of each RS-
485 network, double-checking his wiring against the
example provided in Section 2–4.

He must also bear in mind proper shield-grounding
considerations – each RS-485 IED grounded at only one

Advertising