3.2.12 Current measurement system (Code 6)

The SEL current measurement system consists of the
sensing component (1) and signal-processing unit (2)

[Fig.17]. SEL sensor is integrated into a specially shaped
upper terminal of the breaker and is connected by a

shielded cable to the signal-processing unit. SEL control

unit is placed in the control-box [Fig. 18].

Fig. 17 SEL current measurement system

SEL may be used for recording DC currents in selected
measurement ranges of 6 kA or 12 kA. Measurement of

rated current values and of the current rise may now be

made directly at the breaker.

The sensor includes Hall-probes and delivers a
proportional signal-output to the SEL control. The signal-

processing unit transforms input signal, into standard

output signals shown in the table below.

The outputs are insulated from the main voltage. The
insulation withstands voltages up to 4 kV RMS and up to

40 kV in peak.

Two versions are available. Standard model (T35) for
ambient temperature –5 °C…+35 °C and the model for
higher temperature (T55) –5 °C…+55 °C.

More details can be found in separate instruction for SEL
usage.

Type

SEL 06-1 06-2 06-4 12-1 12-2 12-4

Input

- 6 kA…+6 kA

-12 kA…+12 kA

U

Ne

[V]

1000 2000 4000 1000 2000 4000

T35

for ambient temperature of the breaker
-5 °C…+35 °C / +23 °F…+95 °F

T55

for ambient temperature of the breaker
-5 °C…+55 °C / +23 °F...+131 °F

I

Ne

Relating to the rated current of the breaker

Output 4...20

mA

-20...20 mA

-10...10 V

U

Ni

[kV] 12 18 40 12 18 40

3.2.13 Electronic control system

All the control PCBs are installed in control box [Fig. 18].

Starting from the left, these are:

Fig. 18 Control box with control units

(1) NEKO control unit [Fig. 19-1] (Code 12) – internal
control unit with capacitor bank. Releases firing signal for

ED coil (-X2 :10/:11) and provides indication of the

capacitors charging (-X3 :6/:7). NEKO control unit also
blocks the firing signal until C-bank is fully charged

(~15 sec).

WARNING: NEKO unit requires a high quality firing signal.
Be sure, that voltage level is between 6 V…24 V DC and
there are no short spikes on signal (<3 ms). This might

lead to major defect of the NEKO control unit!

Fig. 19-1 NEKO control unit

(2) Internal voltage converter (Code 8) - converts

external supply voltage (-X3 :4/:5) to the internal
24 V DC. Required by controls (except for the drive

supply).

Fig. 19-2 Voltage converter 110 V/24 V DC.