GE Industrial Solutions GERAPID 2607, 4207, 6007, 8007 with arc chutes 1X2, 1X4, 2X2, 2X3, 2X4 User Manual

Page 14

Advertising
background image

14

Design and specifications are subject to change without notice

S47183e rev.03 2010-06-07

Control box terminals

1x12-pole

AC 400 V, 20 A

4x15-pole

AC 250 V, 8 A

Closing solenoid drive

1)

Rated voltage

AC 48 V - 230 V and DC 48 V - 220 V

Operating range

80 % - 115 % of rated voltage

Power consumption Gerapid 2607 / 4207

1750 W / 2000 W

Power consumption Gerapid 6007 / 8007

2600 W / 2600 W

Minimal CLOSING command duration

100 ms

min.interval between two "CLOSE" operations

~8 s w/o NEKO installed; ~14 s with NEKO

Internal voltage converter

1)

Input: Voltage range

DC 33 - 85 V

for Gerapid 2607, 4207, 6007, 8007

Output: Voltage range

DC 24 V (±5%)

Current

6 A permanent

Model description

PCMD 150 48 S24W-GE

Input: Voltage range

DC 88 - 145 V

Output: Voltage range

DC 24 V (±5%)

Current

6 A permanent

Model description

PCMD 150 110 S24W-GE

Input: Voltage range

AC 115 - 240 V, DC 125 - 353 V

Output: Voltage range

DC 24 V (±5%)

Current

3 A permanent, 5 A/100 ms

Model description

PCMA 70 S24W-GE

External power supply

with plug and socket unit

requires extrnal 24 V (±5%) DC

Aux. contact HS 1…HS 10,

Rated operational voltage Ue/AC

230 V

OC trip target (code 10)

Rated operational current Ie/AC-15

1 A

Arc chutes indicator (code 17)

Conventional thermal current Ie/AC-12 (Ith)

10 A

Rated operational voltage Ue/DC

110 V / 220 V

Rated operational current Ie/DC-13

0.5 A / 0.3 A

Minimum current/voltage ratings

0,1 mA / 6 V DC

Contact duty (min. value)

DC 10 V / 2 mA

Shunt trip standard

Rated voltage/power Uc/Pc

24 V / 100 W

Operating range: OFF

21.6 V - 26.4 V

Shunt trip double winded

Rated voltage/power Uc

DC 110 V/ DC 125 V/ DC 220 V

Rated power for a single winding Pc

230 W

UVR

Rated voltage Uc

24 V

(Zero voltage release)

Operating range: OFF

< 4 V

Operating range: ON

24 V (±10%)

Power consumption

~ 10 W

ED impulse release

Energie source: Capacity

2000 µF

Charging voltage

300 V

Switching interval

max. 2/min with 10 consecutive operations

Endurance

1 000 operations with 1 operation per 180 s

Firing signal level / duration

6 - 24 V / 100 - 1000 ms

Charging signalization relay AC duty :

AC 250 V/ 0.5 A - AC 120 V /1 A

DC duty : DC 220V/0.1A - DC 125V/0.3A - DC 10V/3A

1)

Standard ambient conditions acc. to EN 50123-1 Attachement B. For meeting outside of this standard range, please call back.

Table 2a: Technical data of auxiliary circuits

Components

Technical datas of control circuits
Us / In

SU-Control

CLOSE-push-button -S1

DC 24 V / approx. 10 mA

ST releasing

push-button-S2

DC 24 V / approx. 4 A

UVR releasing

push-button -S2 ( -X2 :6 / :7)

DC 24 V / approx. 10 mA

push-button -S2 ( -X2 :8 / :9 )

DC 24 V / approx. 450 mA

ED-coil tripping w/o NEKO

push-button -S3

DC 300 V / 750 A / 3 ms

ED-coil tripping with NEKO

Connect "Firing signal" at ( -X2 :10 / :11 )

DC 6 V…24 V / approx.20 mA

Table 2b: Control circuits ( directional values to rate the components )

Advertising