3 electrical diagrams, 1 wiring code, Fig. 22 example code shown on the nameplate – GE Industrial Solutions GERAPID 2607, 4207, 6007, 8007 with arc chutes 1X2, 1X4, 2X2, 2X3, 2X4 User Manual

Page 17: Indication of components

Advertising
background image

2010-06-07 S47183e rev.03

Design and specifications are subject to change without notice

17

4.3 Electrical diagrams

4.3.1 Wiring code

The main circuits are not shown in the wiring diagrams
for transparency. The control circuit is presented as a
typical circuit diagram and is a combination of numbered

basic diagrams for drives, trips and indicators.

Using the key numbers of the basic plan, you can derive
the number of the complete diagram.

WARNING: Some non standard electrical circuits do not
comply with the diagrams in this instruction. Such circuits

are coded with unique numbers i.e 36/0033. In such a
case an appendix to this instruction is delivered, which

contains relevant electrical diagrams.

Coding positions:

Key position:

1

/ 2 3 4 5 6 7 8

Breaker type

Aux. voltage supply

ED impulse release

Closing drive

Aux. tripping device

Indicators

Aux. switches

SEL system

EXAMPLE:

Key number:

36 / 1

0 20 20 01

1

Gerapid

With voltage converter

Without ED and NEKO

With closing drive

With UVR release

With OCT trip target

With 3 aux. switches

Without SEL system

Fig. 22 Example code shown on the nameplate.

Key

position

Key

number

Designation

Type
1 36 Gerapid
Auxiliary voltage
2 1 Voltage

converter

2

DC 24 V external supply

Tripping coil
3 0 Without

ed-trip

coil

1

With ed-trip coil

2

With ed-trip coil and NEKO
control unit

Drive
4

20

Solenoid drive with

SU control unit

Tripping device
5 00 Without

trip

unit

10

With

shunt

trip

20

With zero voltage release

Indication device
6 00 Without

indicators

01

OCT trip target

02

Arc chute indicator

03

OCT + arc chute indicator

Auxiliary contacts
7

1

3 auxiliary contacts

2

5 auxiliary contacts

3

10 auxiliary contacts

Current-measurement system
8 S with

SEL


Indication of components

Q1

Impulse ED coil

Q2

Closing drive coil

S1 Push

button

„CLOSE“

S2

Push button „OPEN“, type NO

S3

Push button “OPEN”, type NC

SU control PCB:

K1 Closing

relay

K2

Internal closing stop relay

1)

Shunt trip, zero voltage release PCB:
K1

Internal closing stop relay

1)

K2 Tripping

relay

HS11

Shunt trip self cut-off auxiliary contact

ED-tripping device with internal NEKO PCB:
K1

Voltage monitoring relay

K2

Internal closing stop relay

1)

1)

These relays are part of internal closing stop circuit.

It is a 24 V DC closed circuit, through all PCBs in the box,
except SEL. Serial connection of all relays is realized
through connections ( :5/:6) in each PCB. This circuit
provides priority of a tripping signal over a closing signal.
Additionally it prevents from closing the internal supply
24 V DC lost at UVR PCB or NEKO PCB.

Advertising