Fig. 42 Inspection of the arc chute

6.1.4 Inspection of the contact system
Pay attention to the warnings, Section 1!

A) Remove the arc chute

[Fig. 41]. Loosen the clamping screws (3) and (4), using
SW5 hexagon wrench and take off the arch chute (1)
from the adapter (2).

B) Remove the arc chute adapter

[Fig. 43]. To dismantle the arc chute adapter, loosen and
pull out the four upright screws (1) using SW5 tool. Pay

attention that no screws or washers fall inside the

breaker!

[Fig. 43]. Draw aside and lift off both parings of adapter
(2). Then pull out two protective walls (3).

Fig. 43 Adapter and protective walls

Fig. 44 Checking the contact system

C) Check the protective walls

[Fig. 44]. The material burn out on the protective walls (5)
shall not exceed 1 mm [0.04 in] at any place.


D) Check the arc runners

[Fig. 44]. The arc runners should not be burned more
than 30 % of its total cross section. Pay particular
attention to the area around arc runner bend (3) and at

contact point with arcing contact (2).


E) Check the arcing contact

[Fig. 44]. Wear of the arcing contact (1) must not exceed
2 mm [0.08 in] of its depth. Replace the arcing contact in

that case. If contact erosion exceeds 4 mm [0.16 in],
major contact system failure is possible.

F) Check the main contacts

[Fig. 44]. The main contacts (4) shall not show any
particular signs of material erosion, since the arc is

ignited between the arcing contacts. It means, that for

rated and overload currents there should be no erosion
of main contacts.

Erosion of main contacts can take place only in case of
excessively worn, highly burned arcing contact or during

very high short circuit currents. In that case wear must
not exceed 1.5 mm [0.06 in].

G) Install the adapter

[Fig. 43]. Install the two protective walls (3). Use new ones
if necessary. Install two parings of adapter (2) and

tighten screws (1) use 10 Nm [88 in-lbs].


H) Install the arc chute

[Fig. 41]. Put arc chute (1) into adapter (2).

[Fig. 41]. Tighten front and backside connections of the
arc runners (3), including lock washer; use 10 Nm [88 in-

lbs].

[Fig. 41]. Tighten front and backside of the arc chute
connections (4), including flat washers; use 5 Nm [44 in-

lbs]. Put on isolation caps (6).