4 troubleshooting – GE Industrial Solutions GERAPID 2607, 4207, 6007, 8007 with arc chutes 1X2, 1X4, 2X2, 2X3, 2X4 User Manual

Page 57

Advertising
background image

2010-06-07 S47183e rev.03

Design and specifications are subject to change without notice

57

7.4 Troubleshooting

Breaker does not CLOSE.

A) Closing drive doesn't operate electrically but it is still
possible to close the breaker manually by mean of the

hand lever.

1)

Check the supply voltage of the drive (-X2 :1/:2). The

voltage shall not be less than 80% of drive’s rated
voltage.

2)

Check the supply voltage of the controls (-X3 :4/:5).

The voltage shall not be less than minimum input voltage
required for installed voltage converter

3)

Calculate the voltage drop at both supply lines and

check for adequate wire size.

4)

Check the polarity of the supply connections.

5)

Check continuity of the control connections.


Open the control box:

WARNING ! Following operations are done with control
voltage connected. Only trained specialist or GE Service

representative shall perform them. Risk of electric shock!


6)

Check if the PCBs’ plugs are connected and

screwed.

7)

Check if there is 24 V DC available at output of the

voltage converter. Check -X10 (:8:9:10) / (:6:7).

8)

Check the status of the red LED diode on the SU

PCB.

-

Does not light – power supply failure;

-

Weak light – system ready to CLOSE;

-

Intensive red light – system not ready to

CLOSE. Closing STOP circuit is active, or NEKO PCB is

not charged, or “anti-pumping” is active for 15 sec.

9) Check if the Closing STOP circuit is not open.

Measure voltage at SU PCB, (-X12 5:/:6). There shall

be ~24 V DC available for actuation of “closing stop

relay”. If there is no 24 V DC, check continuity of
closing STOP circuit. Check relays at ST/UVR/NEKO

PCBs, by controlling state of contacts at points :5/:6

of each.

10)

Replace any ST/UVR/NEKO if necessary.

11)

Replace the SU control PCB.

12)

Switch OFF the power at control box! Check

continuity and resistance of solenoid winding. Replace

the solenoid in case of winding breakage.

Contact GE Service in case the problem is not solved.

B) Closing drive operates electrically, but it is not possible
to keep contacts closed.

1)

Check the forced tripping release (if installed). A

permanently blocked tripping device, during closing

operation, will cause closing failure and force contact

opening.

2)

Check contact system area. Look for any parts that

may be stuck between contacts or into mechanism

module.

3)

If the zero voltage release is installed, check

connection of (–S2) pushbutton. If only NO type (-X2 :6/:7)

is used, be sure that (–X2 :8/:9) is shorted.

Open the control box (only when UVR is installed).

4)

Check the wiring connections for UVR PCB.

5)

Check supply of the UVR control PCB (-X13 :7/:8)


Contact GE Service in case the problem is not solved.


Breaker does not OPEN.

WARNING! Below operations are done with control voltage

connected. Only trained specialist or GE Service
representative shall perform them.
Risk of electric shock!

A) Shunt trip does not operate. Breaker is able to CLOSE

and OPEN by means of hand lever.

1)

Check points A2 to A5.

2)

Check the self cut off contact HS11 (-X14 :1/:2).

3)

Check the wiring connections and supply line of ST

PCB (-X14 :7/:8).

4)

Check the continuity of shunt trip coil (-X14 :9/:10).

5)

Replace the ST PCB or ST coil if necessary.


Contact GE Service in case of problem is not solved.

B) Zero voltage release does not operate. Breaker is able to
CLOSE and OPEN by means of hand lever.

1)

Check points A2 to A5.

2)

Check point B3 to B5.

3)

Check the continuity of UVR’s coil (-X13 :9/:10).

4)

Replace the UVR PCB or UVR coil if necessary.

Contact GE Service in case the problem is not solved.


C) ED impulse releasedoes not operate. Breaker is able to

CLOSE and OPEN by means of hand lever.

1) Check points A2 to A5.

2) Check the wiring connections and supply line for NEKO

PCB (-X16 :1/:2).

3) Check the voltage level and timing of firing signal for

releasing the C-bank energy (-X16 :3/:4). Voltage signal
shall be between 6-24 V DC and duration of minimum

3 ms.

4) Check if the NEKO is signaling C-bank charging correctly

(-X16 :9/:10). Relay is closed when NEKO is ready to

operate.

5) Check the continuity of ED coil (-X16 :11/:12).
6) Replace the NEKO PCB if necessary.

Contact GE Service in case the problem is not solved.

Advertising