7 zero voltage release control circuit, Fig. 28 uvr control circuit, 36/ _ _ _ x – GE Industrial Solutions GERAPID 2607, 4207, 6007, 8007 with arc chutes 1X2, 1X4, 2X2, 2X3, 2X4 User Manual

Page 24: X14: uvr pcb

Advertising
background image

24

Design and specifications are subject to change without notice

S47183e rev.03 2010-06-07

4.3.7 Zero voltage release control circuit





























• The closing STOP signal is provided for resetting K2 on the SU-control circuit. It effects with priority in switching

OFF (by ST or UVR) before switching ON. Once switching ON and OFF signals are simultaneous, switching OFF

command will stay longer than switching ON. It means, that OFF command is master command.

• -S2 (-X2 :6/:7) is NO contact, utilized for indirect releasing of the UVR by relay -K2

• -S2 (-X2 :8/:9) is NC contact utilized for direct releasing of the UVR. If it’s not used, please short this connection

permanently.

Fig. 28 UVR control circuit

Key position - 5

Key number - 00: Without shunt trip or zero voltage release.
Key number - 20: With zero voltage release.

36/ _ _ _ X _ _ _

-K2

-K1

-K2

-X14: UVR PCB




[ 1 ]

[ 2 ]



[ 3 ]


[ 4 ]

[ 5 ]

[ 6 ]


[ 7 ]



[ 8 ]





[ 9 ]


[ 10 ]

-X10/11


[ 7 ](-)

DC 24 V


[ 9 ] (+)

-S2

-X2



[ 9 ]


[ 8 ]





[ 7 ]

[ 6 ]

-S3

UVR coil



U<

Closing

STOP relay

-K1