6.6 EVENTS (ALARMS AND MESSAGES)


Each of the following listed events can be displayed on the LCD screen or on PC where the “PowerJump
Manager”
or “PowerJump DataShield” is installed.

Alarms and Messages are differently specified because the alarms are indicating an abnormal
functioning of the UPS (which are additionally signalled with the LED alarm and acoustically with the
buzzer), while the messages indicate the various states of operation of the UPS (stored in the events list,
but not activating the LED alarm and the buzzer).


When in the alarms mode, the LCD screen displays a time ordered sequence of screens corresponding
to the last 256 alarms and messages, each screen indicating:

01.01.2005 12:45:07
NR=255 Status=4A61

4115: LOW

BATTERY VOLTAGE

metering

alarms

parameters

+

ok

1- The date and time when the event occurred.
2-
The number of the event (255 = the most recent).

The standard code and the status word.

3- Code with an explicit text description of the events.



6.6.1 Alarms list

Code

Alarms

Meaning

4000

SETUP VALUES

LOST

Parameters are lost and have been replaced with default values.
Call nearest Service Center for intervention.

4004

UPS

FAILURE

The master unit detected the slave unit missing on the
communication bus even though switch Q1 is still closed.

4100

RECTIFIER FUSES

FAILURE

The u-switch mounted on the Rectifier Input Fuses indicates a
blown fuse, and consequently shut down.
Clearance of this condition allows you to restart the Rectifier.

4102

K4 CLOSING

FAILURE

K4 not closed despite a closing command being issued.
Signalled by auxiliary contact.
Rectifier cannot start.

4103

K4 OPENING

FAILURE

K4 not open despite an opening command being issued.
Signalled by auxiliary contact.
Utility remains connected to Rectifier bridge.

4104

BATTERY

FUSES

This function, when enabled on input programmable relays
(password required), warns the user about the external Battery
Fuses
failure or MCB opening, signalled by NO free contact.

4105

RECTIFIER

OVERTEMPERATURE

Temperature sensor indicates an over temperature on the
Rectifier Bridge.
Only alarm is given.
The Rectifier, when in Off state, cannot start as long as this
condition persists.

4106

RECTIFIER

TRANSFORMER

OVERTEMPERATURE

The temperature sensor inside the input transformer winding
indicates over temperature.
Only the alarm is given.
The Rectifier, when in Off state, cannot start as long as this
condition persists.

4110

RECTIFIER UTILITY

OUT OF TOLERANCE

Rectifier Input Utility is out of tolerance (voltage, frequency or
phase).